Plan Review Notes
Plan Review Notes For Permit 17061225
Permit Number 17061225
Review Stop M
Sequence Number 2
Notes
Date Text
2017-08-17 10:17:06NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- REVISE THE DUCT SIZE SPECIFIED FOR THE MASTER
 BEDROOM RETURN AIR TRANSFER DUCT TO COMPLY WITH SEC.
 M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). NEED TO
 CONSIDER ALL THE SUPPLY AIR ENTERING THE MASTER BEDROOM
 AS REQUIRED BY EXCEPTION #3 OF SEC. M1602.4. . THIS
 INCLUDES THE BATHROOM AND CLOSETS.
 RESPONSE: DUCT WAS REVISED TO 12" DIAMETER. NEED AT
 LEAST 13" DUCT. THERE IS NO 13" DUCT. THEREFORE, NEED
 14" DUCT. REVISE AS REQUIRED.
  
 2- CALCULATIONS TO HAVE THE ENGINEER'S SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 RESPONSE: CALCULATIONS WERE DONE BY LILLIAN GONZALEZ
 "GOARCH ENGINEERING, INC.". NEED THE ENGINEER'S SEAL
 AND SIGNATURE.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWIINGS FOR REFERENCE TO EXPEDITE THE REVIEW PROCESS.
  