2017-08-17 10:17:06 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL |
| REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- REVISE THE DUCT SIZE SPECIFIED FOR THE MASTER |
| BEDROOM RETURN AIR TRANSFER DUCT TO COMPLY WITH SEC. |
| M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). NEED TO |
| CONSIDER ALL THE SUPPLY AIR ENTERING THE MASTER BEDROOM |
| AS REQUIRED BY EXCEPTION #3 OF SEC. M1602.4. . THIS |
| INCLUDES THE BATHROOM AND CLOSETS. |
| RESPONSE: DUCT WAS REVISED TO 12" DIAMETER. NEED AT |
| LEAST 13" DUCT. THERE IS NO 13" DUCT. THEREFORE, NEED |
| 14" DUCT. REVISE AS REQUIRED. |
| |
| 2- CALCULATIONS TO HAVE THE ENGINEER'S SEAL AND |
| SIGNATURE AS REQUIRED BY CHAPTER 471 WHEN SUBMITTING |
| DOCUMENTS FOR PUBLIC RECORDS. |
| RESPONSE: CALCULATIONS WERE DONE BY LILLIAN GONZALEZ |
| "GOARCH ENGINEERING, INC.". NEED THE ENGINEER'S SEAL |
| AND SIGNATURE. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD |
| DRAWIINGS FOR REFERENCE TO EXPEDITE THE REVIEW PROCESS. |
| |