Plan Review Notes For Permit 17061225 |
Permit Number |
17061225 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-25 18:55:01 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- REVISE THE DUCT SIZE SPECIFIED FOR THE MASTER | | BEDROOM RETURN AIR TRANSFER DUCT TO COMPLY WITH SEC. | | M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). NEED TO | | CONSIDER ALL THE SUPPLY AIR ENTERING THE MASTER BEDROOM | | AS REQUIRED BY EXCEPTION #3 OF SEC. M1602.4. . THIS | | INCLUDES THE BATHROOM AND CLOSETS. | | | | 2- CLARIFY ATTACHMENT OF CONDENSING UNIT. THE MOUNTING | | DETAIL ON SHEET M-1 SPECIFIES (8) HOLD DOWN CLIPS ON | | TWO SIDES. CLARIFY HOW ARE THE (8) CLIPS INSTALLED ON | | TWO SIDES ONLY. SEC. 107.2.1 CITY AMENDMENTS. | | | | 3- CALCULATIONS TO HAVE THE ENGINEER'S SEAL AND | | SIGNATURE AS REQUIRED BY CHAPTER 471 WHEN SUBMITTING | | DOCUMENTS FOR PUBLIC RECORDS. | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD | | DRAWIINGS FOR REFERENCE TO EXPEDITE THE REVIEW PROCESS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|