2017-07-17 09:10:18CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SHOW COMPLIANCE WITH ENERGY CODE FOR LIGHTING: "A
 MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS". A NOTE WILL SUFFICE. FBC EC R404.1
 2. PROVIDE CORRECTED PANEL SCHEDULE. CIRCUITS 15, 24,
 SHOULD BE AFCI PROTECTED CIRCUITS. CIRCUIT 29 SHOWS A
 #14 WIRE ON A 20 AMP BREAKER. NEC 215.5, 408.4, ; FBC
 107.2.1, FBC RE3706.1
 3. WIRE FEEDING INTERIOR PANEL FROM OUTSIDE SERVICE IS
 TOO SMALL. 2/0 COPPER CAN ONLY BE USED WHERE IT FEEDS
 100% OF THE LOAD. PROVIDE CORRECTION. NEC 310.15(B)(7);
 FBC RE3602.2
 4. KITCHEN COUNTER OUTLETS SHOW ONLY ONE CIRCUIT (#20).
 CODE REQUIRES MINIMUM OF 2 SMALL APPLIANCE CIRCUITS.
 PROVIDE CORRECTION. NEC 210.11(C)(1), 210.52(B)(3); FBC
 RE3703.2
 5. DINING ROOM LIGHT IS SHOWN ON THE SMALL APPLIANCE
 CIRCUIT FOR THE DINING AREA, WHICH IS NOT PERMITTED PER
 CODE. PROVIDE CORRECTION. NEC 210.11(C)(1),
 210.52(B)(2),(3); FBC RE3703.2
 6. LOAD CALCULATION SHOULD INCLUDE 2 SMALL APPLIANCE
 CIRCUITS. NEC 210.11(C)(1), NEC 220,; FBC RE3602.2
 7. IN SEVERAL LOCATIONS THE OUTLET SPACING IS NOT
 WITHIN THE LIMITS PER CODE: "RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET". PROVIDE CORRECTION. NEC
 210.52; FBC RE3901.2.1
 8. PROVIDE NOTE TO COMPLY WITH CODE FOR LIGHTING IN
 CLOSETS PER NEC 410.16, FBC RE4003.12.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER