2017-07-25 08:37:47NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- THIS PROPERTY WAS SUBDIVIDED INTO TWO LOTS. LOT 11
 AND LOT 12. THIS PERMIT APPLICATION IS FOR THE HOUSE TO
 BE BUILT IN LOT 12. THE PROPOSED ADDRESS FOR LOT 12 IS
 749 TALLAPOOSA STREET. REVISE ADDRESS ON PLANS TO
 REFLECT THE CORRECT ADDRESS. 745 TALLAPOOSA STREET IS
 FOR THE HOUSE TO BE BUILT IN LOT 11. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- PROVIDE SOIL TEST REPORT (2 COPIES) . SEC. R401.4
 FBC-RESIDENTIAL 5TH EDITION (2014).
  
 4- PROVIDE DRAINAGE PLAN ( 2 COPIES) AS REQUIRED BY
 SEC. R401.3 FBC -RESIDENTIAL.
  
 5- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 VALUE TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. THE VALUATION
 WAS UPDATED TO $192,501. THE PERMIT FEE BALANCE IS
 $3,627.36.
  
 6- SHEET 1-4:
 A) THE LOADS SPECIFIED ON THE DESIGN CRITERIA DON'T
 MATCH THE LOADS SPECIFIED ON STRUCTURAL NOTE #2 ON SAME
 DRAWING. REVISE AS REQUIRED TO MATCH. ALSO, THE ATTIC
 LIVE LOAD NEEDS TO BE REVISED IF THE ATTIC ACCESS HAS
 AN STAIR AND FOOTNOTES "B" AND "G" OF TABLE R301.5
 FBC-RESIDENTIAL APPLY.
  
 B) SPECIFY ATTIC ACCESS SIZE. SEC. R807
 FBC-RESIDENTIAL.
  
 C) STRUCTURAL NOTE #2 REFERENCES FBC 2010. THE CURRENT
 CODE IS FBC 5TH EDITION (2014). REVISE AS REQUIRED.
 SEC. 553 F.S.
  
 7- SHEET 3-4: FOUNDATION PLAN IDENTIFIES DETAIL
 SECTIONS 1/S-3 AND 2/S-3. THERE IS NO S-3 SHEET. REVISE
 AS REQUIRED. PROVIDE CORRECT DETAIL REFERENCE. . SEC.
 107.2.1 CITY AMENDMENTS.
  
 8- PLANS NEED TO SPECIFY CARBON MONOXIDE ALARMS FOR ALL
 BEDROOMS. SEE SEC. R315.1 FBC-RESIDENTIAL FOR REQUIRED
 LOCATION.
  
 9- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AND
 DATE BOTTOM OF FORM AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. THE ADDRESS NEEDS TO BE COORDINATED WITH ITEM #2
 ABOVE. THE OWNER NAME DOESN'T MATCH OWNER INFORMATION
 SHOWN ON THE PERMIT APPLICATION AND PBC PROPERTY
 APPRAISER. REVISE AS REQUIRED TO MATCH. ALSO, PROVIDE
 THE BUILDER'S NAME, PERMIT OFFICE AND JURISDICTION
 NUMBER 604700.
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) INSULATION R-VALUE SHOWN ON ITEM #9 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED TO MATCH. SEC. R103.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) PAGE 3 OF 4 IS SHOWING AN ATTIC VENT RATIO OF 1/300.
 TYPICALLY THE VENTILATION RATIO IS 1/150. PERSON
 PREPARING THE ENERGY CALCULATIONS TO PROVIDE DETAILS
 AND SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. R806.2
 FBC-RESIDENTIAL TO GET THE 1/300 VENT RATIO.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED WHEN THE CALCULATIONS ARE NOT USING THE
 SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 10- ENGINEER PLANS NEED TO BE REVISED SHOWING THE
 COMPLIANCE WITH THE 1/300 ATTIC VENT RATIO. COORDINATE
 WITH ENERGY CALCULATIONS SUBMITTED. SEC. R103.2
 FBC-ENERGY CONSERVATION.
  
 11- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 ENGINEER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWIINGS FOR REFERENCE TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712