Plan Review Notes
Plan Review Notes For Permit 17061134
Permit Number 17061134
Review Stop P
Sequence Number 1
Notes
Date Text
2017-07-06 06:35:211) SUBMIT MANUF. SPECIFICATIONS AND SOLAR CERTIFICATION
 FOR THE TANK IN THE GARAGE.WPB AMEND. TO FBC SEC.
 107.2.1.
 2) SHOW THE SIZE OF THE WATER LINES ON THE PLANS.
 SUBMIT A WATER RISER DIAGRAM SHOWING THE REQUIRED
 ISOLATION VALVES FOR THE COLLECTOR, THE PRESSURE AND
 TEMPERATURE RELIEF VALVE, VACUUM RELIEF VALVE, AND
 PROTECTION FROM FREEZING PER THE 2014 FBC-RES.. SECS.
 M2301.2.3, M2301.2.8. M2301.2.4 & M2301.2.5.
 3) SHOW THE REQUIRED EXPANSION TANK FOR THE SYSTEM PER
 2014 FBC-RES. SEC.M2301.2.6.THE TANK SHALL BE SIZED IN
 ACCORDANCE WITH SEC.M2003.
 4) PROVIDE INFORMATION ON THE MAXIMUM TEMPERATURE
 LIMITATION REQUIRED FOR THE HOT WATER PER 2014 FBC-RES.
 SEC.M2301.2.9.
  