Plan Review Notes
Plan Review Notes For Permit 17061123
Permit Number 17061123
Review Stop B
Sequence Number 2
Notes
Date Text
2017-08-22 18:21:30REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) (PREVIOUS COMMENT) SPECIFY THE DESIGN DATA ON THE
 PLANS. PROVIDE THE APPLICABLE CODES, OCCUPANCY TYPE AND
 TYPE OF CONSTRUCTION. FBC-R301 ( THIS IS AN R-3
 OCCUPANCY TYPE AND TYPE VB CONSTRUCTION. )
  
 2) (PREVIOUS COMMENT) FBC-R314.3.1 ALTERATIONS, REPAIRS
 AND ADDITIONS. WHEN ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. SHOW THE
 SMOKE ALARMS ON THE PLANS.
  
 3) (PREVIOUS COMMENT) PROVIDE A DETAIL SHOWING HOW THE
 MASTER BEDROOM WALL WILL BE FILLED IN WHEN THE SLIDING
 GLASS DOOR IS REMOVED. FBC-R601
  
 4) (PREVIOUS COMMENT)THE PROPOSED FAMILY ROOM THAT IS
 SHOWN ON THE PLANS IS CURRENTLY A SCREENED PORCH. THE
 INSTALLATION OF THE SLIDING GLASS DOORS AT THE EXTERIOR
 OF THE SCREEN PORCH ( UNDER PERMIT # 17060843 ) AND THE
 PROPOSED REMOVAL OF THE DOORS BETWEEN THE PORCH AND THE
 EXISTING LIVING SPACE WILL CONVERT THE PORCH TO
 CONDITIONED SPACE. FBC ENERGY CONSERVATION SECTION
 R101.4.5 REQUIRES ANY UNCONDITIONED SPACE THAT IS
 ALTERED TO BECOME CONDITIONED SPACE TO BE BROUGHT INTO
 FULL COMPLIANCE WITH THE ENERGY CODE. SUBMIT TWO SETS
 OF FORMS AND DOCUMENTS TO SHOW COMPLIANCE. FBC ENERGY
 CONSERVATION SECTION R103.
  
 5) (PREVIOUS COMMENT) SHOW THE EXTERIOR WALL AND
 CEILING INSULATION FOR THE ENCLOSED PORCH ( PROPOSED
 FAMILY ROOM ) ON THE PLANS. FBC ENERGY CONSERVATION
 SECTION 402.
  
 6) (PREVIOUS COMMENT) THE PLANS INDICATE THAT
 PREVIOUSLY UNCONDITIONED SPACE IS BEING CONVERTED TO
 HABITABLE SPACE. PROVIDE AREA TABULATIONS ON THE PLANS
 TO SHOW THE SQUARE FOOTAGE OF EXISTING AND PROPOSED
 CONDITIONED AND UNCONDITIONED AREAS. FBC 107.2.1 THIS
 INFORMATION IS PROVIDED ON THE PBC PROPERTY APPRAISERS
 WEBSITE.
  
 7) (PREVIOUS COMMENT) THE PLANS ARE REQUIRED TO BE
 REVIEWED BY PALM BEACH COUNTY FOR IMPACT FEES. BEFORE A
 PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES MUST BE
 PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE SET OF
 PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM BEACH
 COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH THE
 IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT MUST BE
 RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE THE
 BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 8) (PREVIOUS COMMENT)THE VALUATION FOR THIS WORK
 APPEARS TO BE LOW. SUBMIT A COPY OF THE SIGNED
 CONTRACT. FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 9) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  