2017-07-17 08:25:51 | PLAN REVIEW COMMENTS |
| |
| |
| CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: |
| |
| 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN |
| PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS |
| 471.003(2)(H); 471.025; FBC 107.2.1 |
| 2. STATED VALUE OF WORK ON PERMIT APPLICATION SEEMS |
| LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| VALUE OF WORK. FBC 109.3 |
| 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION TO COMPLY WITH CODE. NEC |
| 210.8, 210.12, 215.5, 408.4; FBC RE3706.2, RE3902 |
| 4. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| 5. PROVIDE AND SHOW ON PLAN NEW OUTLETS IN MASTER |
| BEDROOM TO COMPLY WITH WALL SPACING REQUIREMENTS. |
| RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET. NEC |
| 210.52; FBC RE3901.2.1 |
| 6. PROVIDE AND SHOW ON PLAN NEW OUTLETS IN KITCHEN TO |
| COMPLY WITH WALL SPACING REQUIREMENTS. A RECEPTACLE |
| OUTLET SHALL BE INSTALLED AT EACH WALL COUNTERTOP SPACE |
| 12 INCHES (305 MM) OR WIDER. RECEPTACLE OUTLETS SHALL |
| BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS |
| MORE THAN 24 INCHES (610 MM), MEASURED HORIZONTALLY |
| FROM A RECEPTACLE OUTLET IN THAT SPACE. NEC 210.52; FBC |
| RE3901.4.1 |
| 7. SHOW ON PLAN ANY EXISTING SMOKE ALARMS. IF NONE ARE |
| EXISTING, OR NOT TO CODE, SHOW AS NEW INSTALLATION. FBC |
| R314.3.1; FBC 107.2.1 |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |