Plan Review Notes
Plan Review Notes For Permit 17061123
Permit Number 17061123
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-17 08:25:51PLAN REVIEW COMMENTS
  
  
 CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
 2. STATED VALUE OF WORK ON PERMIT APPLICATION SEEMS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK. FBC 109.3
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION TO COMPLY WITH CODE. NEC
 210.8, 210.12, 215.5, 408.4; FBC RE3706.2, RE3902
 4. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 5. PROVIDE AND SHOW ON PLAN NEW OUTLETS IN MASTER
 BEDROOM TO COMPLY WITH WALL SPACING REQUIREMENTS.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET. NEC
 210.52; FBC RE3901.2.1
 6. PROVIDE AND SHOW ON PLAN NEW OUTLETS IN KITCHEN TO
 COMPLY WITH WALL SPACING REQUIREMENTS. A RECEPTACLE
 OUTLET SHALL BE INSTALLED AT EACH WALL COUNTERTOP SPACE
 12 INCHES (305 MM) OR WIDER. RECEPTACLE OUTLETS SHALL
 BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS
 MORE THAN 24 INCHES (610 MM), MEASURED HORIZONTALLY
 FROM A RECEPTACLE OUTLET IN THAT SPACE. NEC 210.52; FBC
 RE3901.4.1
 7. SHOW ON PLAN ANY EXISTING SMOKE ALARMS. IF NONE ARE
 EXISTING, OR NOT TO CODE, SHOW AS NEW INSTALLATION. FBC
 R314.3.1; FBC 107.2.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  