Plan Review Notes
Plan Review Notes For Permit 17061121
Permit Number 17061121
Review Stop E
Sequence Number 2
Notes
Date Text
2017-08-15 08:34:35CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS (2ND REVIEW):
  
 PREVIOUS COMMENTS NOT ADDRESSED, SEE BELOW;
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. FS 471, FAC61G15-23, FBC 107.3.5
 2. SHOW ON PLAN THE LOCATION OF ANY EXISTING SMOKE
 ALARMS. IF NONE ARE EXISTING, OR NOT TO CODE, SHOW AS
 NEW INSTALLATION. FBC 907.2.11
 3. SHOW ON PLAN ANY NEW OR ALTERED CIRCUITS AND OUTLETS
 REQUIRED FOR WALL SPACE IN NEW WALLS. NEC 210.52
 4. PROVIDE PANEL SCHEDULE, INDICATE ANY NEW OR ALTERED
 CIRCUITS, SHOW WIRE AND BREAKER SIZE, INDICATE AFCI OR
 GFCI PROTECTION AS REQUIRED. NEC 210.8, 210.12, 215.5;
 FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  