Plan Review Notes
Plan Review Notes For Permit 17061121
Permit Number 17061121
Review Stop M
Sequence Number 1
Notes
Date Text
2017-07-06 12:07:421ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17061121
 7/6/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED PLANS DO NOT PROVIDE ADEQUATE
 INFORMATION TO PERFORM A FULL REVIEW. PLEASE REVIEW THE
 FOLLOWING WEST PALM BEACH AMENDMENTS TO THE FBC:
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 2) PROVIDE ON THE PLAN A LIST CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROPOSED PROJECT-
 SECTION 107.2.1
  
 3) IDENTIFY ALL ROOMS AND SPACES SHOWN ON THE PLANS-
 107.2.1.
  
 4) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 5) SHOW ALL ALTERATIONS TO THE EXISTING AC SYSTEM
 REQUIRED TO PROVIDE BALANCED AIR FLOW TO THE NEW ROOMS-
 SECTION 601.5.
  
 6) PROVIDE BATHROOM EXHAUST AT A RATE OF 50 CFMS FOR
 INTERMITTENT USE, OR 20 CFMS FOR CONTINOUS USE- TABLE
 403.3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER