2017-07-06 12:07:42 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES |
| PERMIT #17061121 |
| 7/6/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE SUBMITTED PLANS DO NOT PROVIDE ADEQUATE |
| INFORMATION TO PERFORM A FULL REVIEW. PLEASE REVIEW THE |
| FOLLOWING WEST PALM BEACH AMENDMENTS TO THE FBC: |
| |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| ELECTRONIC MEDIA DOCUMENTS SHALL BE |
| SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. (SEE ALSO SECTION 107.3.5). |
| |
| FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| RECORDS MANAGEMENT. |
| |
| 2) PROVIDE ON THE PLAN A LIST CURRENT CODES AND |
| STANDARDS USED IN THE DESIGN OF THE PROPOSED PROJECT- |
| SECTION 107.2.1 |
| |
| 3) IDENTIFY ALL ROOMS AND SPACES SHOWN ON THE PLANS- |
| 107.2.1. |
| |
| 4) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE |
| AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. |
| PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| PROVIDED CFMS OF OUTDOOR AIR. |
| |
| 5) SHOW ALL ALTERATIONS TO THE EXISTING AC SYSTEM |
| REQUIRED TO PROVIDE BALANCED AIR FLOW TO THE NEW ROOMS- |
| SECTION 601.5. |
| |
| 6) PROVIDE BATHROOM EXHAUST AT A RATE OF 50 CFMS FOR |
| INTERMITTENT USE, OR 20 CFMS FOR CONTINOUS USE- TABLE |
| 403.3. |
| |