Plan Review Notes For Permit 17061121 |
Permit Number |
17061121 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-11 09:46:08 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW COMMENTS: | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | SEALED BY DESIGN PROFESSIONAL OR THE ELECTRICAL | | CONTRACTOR QUALIFIER. FS 471, FAC61G15-23, FBC 107.3.5 | | 2. SHOW ON PLAN THE LOCATION OF ANY EXISTING SMOKE | | ALARMS. IF NONE ARE EXISTING, OR NOT TO CODE, SHOW AS | | NEW INSTALLATION. FBC 907.2.11 | | 3. SHOW ON PLAN ANY NEW OR ALTERED CIRCUITS AND OUTLETS | | REQUIRED FOR WALL SPACE IN NEW WALLS. NEC 210.52 | | 4. PROVIDE PANEL SCHEDULE, INDICATE ANY NEW OR ALTERED | | CIRCUITS, SHOW WIRE AND BREAKER SIZE, INDICATE AFCI OR | | GFCI PROTECTION AS REQUIRED. NEC 210.8, 210.12, 215.5; | | FBC 107.2.1 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|