Plan Review Notes
Plan Review Notes For Permit 17061109
Permit Number 17061109
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-06 10:52:03FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 WIRES FROM METER TO TRANSFER SWITCH AND TO THE PANEL
 FROM TRANSFER SWITCH SHOWS #1, PANEL AND TRANSFER
 SWITCH SHOW 200AMPS
 PLEASE SHOW SIZE OF MAIN IN METER MAIN COMBO.
  
 METER MAIN COMBO NEEDS TO BE THE RINGLESS TYPE OR FPL
 WILL NOT SET METER.