2017-06-29 12:30:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) WILL THIS PROPOSED GENERATOR PROVIDE BACKUP |
| EMERGENCY POWER TO ANY LIFE SAFETY SYSTEM.I.E FIRE |
| ALARM OR FIRE SPRINKLER? |
| |
| IF SO, IT SHALL COMPLY WITH NFPA 110. PLEASE PROVIDE AN |
| APPLICABLE NOTE AND ENSURE COMPLIANCE. |
| |
| |
| |
| 2) THE ATTACHED DATA SHEETS INDICATE THE PROPOSED WILL |
| BE FUELED BY LP AND/OR NG. PLEASE CONFIRM. |
| |
| THE FUEL SUPPLY SHALL BE UNDER SEPARATE PERMIT IF NOT |
| DONE BY THIS CONTRACTOR OR SPECIFICALLY INDENTIFIED |
| UNDER THIS PERMIT WILL ALL APPLICABLE DRAWINGS SHOWING |
| LOCATION AND SIZE OF ALL PIPE CONNECTIONS, LOCATION AND |
| SIZE OF PROPOSED PIPE, DEPTH OF COVER, ETC., AND |
| EQUIPMENT SPEC SHEETS. |
| |
| |
| |
| 3) THE ARE NO DRAWINGS OF FOUNDATION PLANS OR HOW IT |
| WILL BE SECURED TO THE FOUNDATION. THERE ARE NO |
| DIMENSIONS FROM THE BUILDING. |
| |
| PLEASE PROVIDEAND ENSURE COMPLIANCE WITH THE APPLICABLE |
| CODE. |
| |
| |
| |
| 4) PLEASE PROVIDE DIMENSIONS OF THE NEAREST WINDOW AND |
| OR DOOR TO ENSURE THE SEPARATION DISTANCES REQUIRED |
| THAT AVOIDS FUMES ENTERING THE BUILDING. THERE IS NO |
| INDICATION OF EXHAUST LOCTION. |
| |
| PLEASE PROVIDE. |
| |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| |