Plan Review Notes
Plan Review Notes For Permit 17061090
Permit Number 17061090
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-28 07:57:25 
 CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. IN SUBMITTED SPEC SHEETS, NOR ON PLAN, IS THE MODEL
 OF THE TRANSFER SWITCH OR GENERATOR IDENTIFIED. PROVIDE
 DETAILS OF GENERATOR ON PLAN, INDICATE WHICH MODEL OF
 TRANSFER SWITCH AND GENERATOR WILL BE USED ON SPEC
 SHEETS, AND SHOW LOCATION OF TRANSFER SWITCH (LOCATED
 INSIDE OR OUTSIDE). FBC 107.2.1; NEC 702.4, 110.9
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  