2017-07-31 09:42:092ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17061037
 7/31/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW EXHAUST HOOD HAS A CAPACITY OF 600 CFMS
 WHICH REQUIRES MAKEUP AIR TO BE PROVIDED PER SECTION
 505.2. PLEASE REVISE THE PLAN TO SHOW HOW THE AIR WILL
 BE PROVIDED, AND SHOW THE EXHAUST DUCT RUN AND POINT OF
 CONNECTION TO THE EXISTING DUCT.
  