Plan Review Notes For Permit 17061037 |
Permit Number |
17061037 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-07-31 09:42:09 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17061037 | | 7/31/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE NEW EXHAUST HOOD HAS A CAPACITY OF 600 CFMS | | WHICH REQUIRES MAKEUP AIR TO BE PROVIDED PER SECTION | | 505.2. PLEASE REVISE THE PLAN TO SHOW HOW THE AIR WILL | | BE PROVIDED, AND SHOW THE EXHAUST DUCT RUN AND POINT OF | | CONNECTION TO THE EXISTING DUCT. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|