2017-07-03 15:57:231ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17061037
 7/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) EXHAUST VENTILATION FOR THE KITCHEN IS REQUIRED AT A
 RATE OF 100 CFMS PER SQ. FT. FOR INTERMITTENT OPERATION
 OR 25 CFMS PER SQ. FT. FOR CONTINUOUS OPERATION- TABLE
 403.3
  
 2) PROVIDE AN EXHAUST HOOD AND DUCT SYSTEM FOR THE
 COOKTOP. PROVIDE DETAILS ON THE PLAN AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- SECTION 505.2.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 DRYER AND SHOW EXHAUST DUCT ALTERATIONS- SECTION 504.4.
  