Plan Review Notes For Permit 17061037 |
Permit Number |
17061037 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-03 15:57:23 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17061037 | | 7/3/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) EXHAUST VENTILATION FOR THE KITCHEN IS REQUIRED AT A | | RATE OF 100 CFMS PER SQ. FT. FOR INTERMITTENT OPERATION | | OR 25 CFMS PER SQ. FT. FOR CONTINUOUS OPERATION- TABLE | | 403.3 | | | | 2) PROVIDE AN EXHAUST HOOD AND DUCT SYSTEM FOR THE | | COOKTOP. PROVIDE DETAILS ON THE PLAN AND SUBMIT | | MANUFACTURER'S SPECIFICATIONS- SECTION 505.2. | | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW | | DRYER AND SHOW EXHAUST DUCT ALTERATIONS- SECTION 504.4. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|