Plan Review Notes
Plan Review Notes For Permit 17061034
Permit Number 17061034
Review Stop M
Sequence Number 1
Notes
Date Text
2017-07-03 15:37:241ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17061034
 7/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.1 & 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) EXHAUST VENTILATION AT A RATE OF 0.70 CFMS PER SQ.
 FT. IS REQUIRED FOR THE KITCHEN- TABLE 403.3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER