2017-07-05 08:56:03 | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | NFPA 70 2011 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | C405.2.2.2 OCCUPANCY SENSORS. | | OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS, | | CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND | | BREAK ROOMS, PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS | | AND JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE | | FEET (28 M2) OR LESS ENCLOSED BY FLOOR-TO-CEILING | | HEIGHT PARTITIONS. THESE AUTOMATIC CONTROL DEVICES | | SHALL BE | | INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS WITHIN 30 | | MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND SHALL | | EITHER | | BE MANUAL ON OR SHALL BE CONTROLLED TO AUTOMATICALLY | | TURN THE LIGHTING ON TO NOT MORE THAN 50 PERCENT POWER. | | |
|