2017-06-29 09:26:14 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17061034 |
| ADD: 310 S. DIXIE HWY. SUITE 300 & 302 |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 973-941-7444 |
| E-MAIL: ?????? WE PREFER E-MAIL FOR CORRESPONDENCE!!! |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. JUNE 29 |
| ACTION: DENIED |
| |
| 1) SHEET D-1: |
| 1A) SHEET D-1 SHOWS THE FRONT ENTRY WALL (BOWED WALL) |
| BEING REMOVED AN APPROXIMATE 30 FOOT SECTION OF WALL. |
| SHEET 1.0A SHOWS A STRAIGHT SECTION OF WALL WITH |
| APPROX.. A 45 DEGREE TURN AND A 42 INCH SECTION OF |
| WALL, 2 WINDOWS AND ONE DOOR AND SHEET 1.3A THE |
| ELEVATION SHEET SHOWS A TRANSOM HORIZONTAL MULLION, |
| WINDOWS AND DOOR. PLEASE PROVIDE A CUT SECTION THROUGH |
| THIS PORTION OF NEW WALL. ON THE EXTERIOR CEILING THERE |
| WILL BE CEILING MISSING SINCE THE BOWED FRONT WAS |
| REMOVED, HOW WILL THIS NEW WALL SECTION TIE INTO THE |
| FLOOR FRAMING SYSTEM? THE PLANS INDICATE USE THE |
| EXISTING HEADER? TYPE OF MATERIAL? 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED? THIS WALL SECTION WILL BE PART |
| OF THE MWFRS (MAIN WIND FORCE RESISTING SYSTEM) PLEASE |
| SHOW CONNECTIONS FBC-B 1609.6.4. |
| |
| 1B) THIS SAME WALL SECTION SHOWS THE TRANSOM ABOVE AND |
| A HORIZONTAL FRAMING MEMBER SEPARATING THE TRANSOM |
| ABOVE FROM THE DOOR AND WINDOWS BELOW. WHAT SUPPORTS |
| THE HORIZONTAL FRAMING MEMBER AT THE 45 DEGREE TURN? IS |
| THERE A COLUMN NOT SHOWN, OR A 45 DEGREE ALUMINUM |
| MULLION? PLEASE SHOW THE VERTICAL FRAMING MEMBER AS |
| WELL, AND SHOW HOW BOTH THE HORIZONTAL AND VERTICAL |
| FRAMING MEMBERS ARE GOING TO BE ANCHORED. MAYBE |
| CONSIDERED AS MWFRS OR COMPONENTS AND CLADDING |
| DEPENDING ON THE MATERIALS USED AND IF THERE IS PRODUCT |
| APPROVALS. |
| |
| 1C) SHEET 1.3A SECTION 3-1.3A SHOWS THE TRANSOM LITES |
| AND HEADER NOT BEING MOVED, THEN WHAT MATERIAL WILL BE |
| USED FOR INFILL BETWEEN THE BOWED SECTION ABOVE THAT |
| STAYS AND THE NEW SECTION BELOW THAT SHOWS A STRAIGHT |
| SECTION OF WALL WITH A 45 DEGREE TURN AN 42 INCH |
| SECTION OF WALL?107.2.1.3 ADDITIONAL INFORMATION |
| REQUIRED. |
| IF THIS DETAIL IS NOT CORRECTLY ILLUSTRATED AND THE |
| TRANSOMS ARE TO BE REUSED AND REINSTALLED PLEASE |
| PROVIDE THE INFORMATION ON THE WINDOW SASH, HOW WILL |
| THEY BE RE-INSTALLED, DOES THE PRESENT GLAZING MEET THE |
| WIND DESIGN PRESSURES OF TODAY, AND WITH BEING |
| REINSTALLED HOW WILL THEY MEET THE REQUIREMENTS FOR |
| LARGE MISSILE IMPACT TESTING OR BE SHUTTERED. |
| 1609.6.4.4 APPLICATIONS OF WIND PRESSURE. |
| 2404.1 VERTICAL GLASS. |
| 2) SHEET 1.3A THE WIND DESIGN CRITERIA IS GIVEN |
| CORRECTLY BUT NOT THE PRESSURES ASSOCIATED WITH THE |
| DESIGN. |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. (5.) DESIGN WIND |
| PRESSURES. |
| 3) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| VENTILATORS |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| 4) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 6) SHEET 1.0A DOOR # 1 IS MISSING ON THE PLANS & DOOR # |
| 6 IS THIS A INTERIOR DOOR NEEDING FIRE RATING OR IS |
| THIS A EXTERIOR DOOR? 107.2.1.3 ADDITIONAL INFORMATION |
| IS REQUIRED. |
| |
| 7) SHEET1.2A THE REAR EXIT DOOR FROM THE DINING AREA |
| DOES NOT HAVE THE REQUIRED 18 INCHES AT THE LATCH SIDE |
| OF THE DOOR. PLEASE SHOW COMPLIANCE WITH: 2014 FBC |
| ACCESSIBILITY CODE 404.2.4 OR |
| 404.3 AUTOMATIC AND POWER-ASSISTED DOORS AND GATES. |
| 404.3.2 MANEUVERING CLEARANCE. |
| CLEARANCES AT POWER-ASSISTED DOORS AND GATES SHALL |
| COMPLY WITH 404.2.4. CLEARANCES AT AUTOMATIC DOORS AND |
| GATES WITHOUT STANDBY POWER AND SERVING AN ACCESSIBLE |
| MEANS OF EGRESS SHALL COMPLY WITH 404.2.4. |
| |
| EXCEPTION: WHERE AUTOMATIC DOORS AND GATES REMAIN OPEN |
| IN THE POWER-OFF CONDITION, COMPLIANCE WITH 404.2.4 |
| SHALL NOT BE REQUIRED. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |