Plan Review Notes
Plan Review Notes For Permit 17061005
Permit Number 17061005
Review Stop M
Sequence Number 4
Notes
Date Text
2017-12-13 11:03:564TH REVIEW FBC-2014 MECHANICAL
 PERMIT #17061005
 12/13/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 MANY OF THE PREVIOUS COMMENTS STILL EXIST. PER
 TELEPHONE CONVERSATION WITH MIGUEL OF GLIDDEN-SPINA THE
 CIMMENTS LISTED BELOW ARE UNDERSTOOD AND WILL BE
 ADDRESSED ON THE NEXT PLAN SUBMISSION.
  
 1) SHEETS: A1.1 & A1.3 STILL SHOW THE AC CLOSET DOOR
 OPENING INTO THE KITCHEN.
  
 2) SHEET A2 IS STILL INDICATING THE AC CLOSET DOOR TO
 BE WOOD AND NOT NON-COMBUSTIBLE.
  
 3) REQUESTED AC COOLING AND HEATING CALCULATIONS NIT
 SUBMITTED.
  
 4) UL 197 LISTING AND LABELING FOR THE ELECTRIC COOKING
 APPLIANCE NOT VERIFIED ON THE VENTLESS HOOD SUBMITTAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  