2017-11-02 08:40:56 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #17061005 |
| 11/2/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| THE COMMENTS FROM THE 2ND REVIEW WERE NOT ADDRESSED AND |
| STILL EXIST. THOSE COMMENTS ARE PRINTED BELOW AN |
| ADDITIONAL REVIEW COMMENTS BASED ON THE RESUBMITTED |
| PLANS. |
| |
| 1) THE REVISED M2.1 PLAN SHOWS THE AC CLOSET LOUVERED |
| DOOR RELOCATED TO THE WALL BETWEEN THE CLOSET AND THE |
| KITCHEN. PLEASE REFER TOTABLE 403.3 FOOTNOTE B. AND |
| SECTION 403.2.1(3) WHICH PROHIBITS AIR FROM THE KITCHEN |
| TO BE RECIRCULATED TO THE DINING ROOM. ALL AIR TO THE |
| KITCHEN SHALL BE EXHAUSTED. |
| |
| 2) SHEET A2.0: AS PREVIOUSLY NOTED IN THE 1ST REVIEW, |
| THE AC CLOSET DOOR SHALL BE NON-COMBUSTIBLE, HOWEVER |
| THE SCHEDULE IS STILL INDICATING A WOOD DOOR. |
| |
| |
| 2ND REVIEW FBC-2014 MECHANICAL |
| PERMIT #17061005 |
| 8/17/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) ACCORDING TO THE MANUFACTURER'S SPECIFICATIONS 400 |
| CFMS OF FRESH AIR IS REQUIRED AS MAKEUP AIR FOR THE |
| VENTLESS HOOD, HOWEVER NO AIR IS BEING PROVIDED PER THE |
| AC EQUIPMENT SCHEDULE AND THE VENTILATION CALCULATIONS. |
| PLEASE NOTE THAT THE SPECS ARE ALSO RECOMMENDING 400 |
| CFMS OF FRESH AIR OUTSIDE OF THE COOKING AREA OR THE |
| DINING AREA, HOWEVER THE SCHEDULE INDICATES ONLY 325 |
| |
| CFMS OF AIR BEING PROVIDED THERE- SECTION 507.2.1. |
| |
| 2) PROVIDE DOCUMENTATION THAT THE COOKING APPLIANCE IS |
| LISTED AND LABELED IN ACCORDANCE WITH UL 197- SECTION |
| 917.1. |
| |
| 3) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| NEW AC SYSTEMS- SECTION C403.2.1 FBC-14 ENERGY |
| CONSERVATION. |
| |
| 4) PLEASE PLACE A NOTE ON THE PLANS INDICATING A |
| SEPARATE PERMIT IS REQUIRED FOR INSTALLATION OF THE |
| VENTLESS HOOD AND INTEGRAL FIRE SUPPRESSION SYSTEM- |
| SECTION 107.1 WPB AMENDMENTS TO THE FBC. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |