Plan Review Notes
Plan Review Notes For Permit 17061005
Permit Number 17061005
Review Stop E
Sequence Number 3
Notes
Date Text
2017-11-13 15:55:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BASED ON NEW SUBMISSION, THE 45 KVA TRANSFORMER IS
 SHOWN OVERLOADED. THE CAPACITY OF A 45KVA TRANSFORMER
 IS 125 AMPS PER PHASE, AND A TOTAL OF 45,000 VA.
 PROVIDE CORRECTION SO THAT TRANSFORMER IS NOT
 OVERLOADED. NEC 110.3, NEC 220
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  