Plan Review Notes
Plan Review Notes For Permit 17061005
Permit Number 17061005
Review Stop M
Sequence Number 2
Notes
Date Text
2017-08-17 10:20:032ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17061005
 8/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ACCORDING TO THE MANUFACTURER'S SPECIFICATIONS 400
 CFMS OF FRESH AIR IS REQUIRED AS MAKEUP AIR FOR THE
 VENTLESS HOOD, HOWEVER NO AIR IS BEING PROVIDED PER THE
 AC EQUIPMENT SCHEDULE AND THE VENTILATION CALCULATIONS.
 PLEASE NOTE THAT THE SPECS ARE ALSO RECOMMENDING 400
 CFMS OF FRESH AIR OUTSIDE OF THE COOKING AREA OR THE
 DINING AREA, HOWEVER THE SCHEDULE INDICATES ONLY 325
  
 CFMS OF AIR BEING PROVIDED THERE- SECTION 507.2.1.
  
 2) PROVIDE DOCUMENTATION THAT THE COOKING APPLIANCE IS
 LISTED AND LABELED IN ACCORDANCE WITH UL 197- SECTION
 917.1.
  
 3) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AC SYSTEMS- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 4) PLEASE PLACE A NOTE ON THE PLANS INDICATING A
 SEPARATE PERMIT IS REQUIRED FOR INSTALLATION OF THE
 VENTLESS HOOD AND INTEGRAL FIRE SUPPRESSION SYSTEM-
 SECTION 107.1 WPB AMENDMENTS TO THE FBC.
  