Plan Review Notes For Permit 17061005 |
Permit Number |
17061005 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-08-17 10:20:03 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17061005 | | 8/17/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) ACCORDING TO THE MANUFACTURER'S SPECIFICATIONS 400 | | CFMS OF FRESH AIR IS REQUIRED AS MAKEUP AIR FOR THE | | VENTLESS HOOD, HOWEVER NO AIR IS BEING PROVIDED PER THE | | AC EQUIPMENT SCHEDULE AND THE VENTILATION CALCULATIONS. | | PLEASE NOTE THAT THE SPECS ARE ALSO RECOMMENDING 400 | | CFMS OF FRESH AIR OUTSIDE OF THE COOKING AREA OR THE | | DINING AREA, HOWEVER THE SCHEDULE INDICATES ONLY 325 | | | | CFMS OF AIR BEING PROVIDED THERE- SECTION 507.2.1. | | | | 2) PROVIDE DOCUMENTATION THAT THE COOKING APPLIANCE IS | | LISTED AND LABELED IN ACCORDANCE WITH UL 197- SECTION | | 917.1. | | | | 3) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | NEW AC SYSTEMS- SECTION C403.2.1 FBC-14 ENERGY | | CONSERVATION. | | | | 4) PLEASE PLACE A NOTE ON THE PLANS INDICATING A | | SEPARATE PERMIT IS REQUIRED FOR INSTALLATION OF THE | | VENTLESS HOOD AND INTEGRAL FIRE SUPPRESSION SYSTEM- | | SECTION 107.1 WPB AMENDMENTS TO THE FBC. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|