Plan Review Notes
Plan Review Notes For Permit 17061005
Permit Number 17061005
Review Stop P
Sequence Number 1
Notes
Date Text
2017-07-06 16:16:301ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. A VENT IS REQUIRED ON THE FLOW CONTROL AT THE INLET
 OF GREASE INTERCEPTOR PER MANUFACTURE INSTALLATION
 GUIDE.
  
 2. A VENT IS REQUIRED ON THE OUTLET OF THE GREASE
 INTERCEPTOR PER MANUFACTURE INSTALLATION GUIDE AND FBC
 PL 901.2- 901.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  