2017-07-06 16:16:30 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. A VENT IS REQUIRED ON THE FLOW CONTROL AT THE INLET | | OF GREASE INTERCEPTOR PER MANUFACTURE INSTALLATION | | GUIDE. | | | | 2. A VENT IS REQUIRED ON THE OUTLET OF THE GREASE | | INTERCEPTOR PER MANUFACTURE INSTALLATION GUIDE AND FBC | | PL 901.2- 901.2.1 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|