Plan Review Notes
Plan Review Notes For Permit 17061005
Permit Number 17061005
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-06-26 15:02:23PERMIT # 17061005
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SHEET CVR: ADDRESS IS LISTED AS BOTH 511 AND 517 N.
 OLIVE AVE. PLEASE ENSURE THAT ONLY THE CORRECT ADDRESS
 IS LISTED ON THE PLANS.
  
 2) SHEET ALS 1.1: OCCUPANCY LOAD IS LISTED AS "9
 PERSONS", HOWEVER THE LAYOUT SHOWS SEATING FOR 17
 PERSONS.
 PLEASE REVISE OCCUPANCY LOAD AND/OR SEATING PLAN TO
 SHOW ACCURATE OCCUPANCY. WHERE POSSIBLE, PLEASE BREAK
 DOWN THE OCCUPANCY LOAD BY DINIING/SEATING AREA,
 QUEUEING, AND KITCHEN LOADS.
  
 3) SHEET ALS 1.1: THE DRAWINGS SHOW A DOOR IN REAR OF
 THE SPACE, PLEASE ADVISE IF THAT IS A 2ND MEANS OF
 EGREES (EMERGENCY EXIT), IF SO, IT NEEDS TO BE
 IDENTIFIED ACCORDINGLY.
 IF IT IS NOT A MEANS OF EGRESS, ALL EXTERIOR DOORS NOT
 FUNCTIONING AS EXITS SHALL BE PERMANENTLY MARKED AND
 CLEARLY INDICATED AS, "NOT AN EXIT."
  
 4) SHEET A1.4: PLEASE PROVIDE MANUFACTURER'S SPECS FOR
 EQUIPMENT ITEM "8" - THE ALL IN ONE VENTLESS COOKING
 SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved