2017-07-05 08:51:47 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: |
| |
| 1. PROVIDE NOTE FOR EXIT AND EMERGENCY LIGHTS TO BE |
| CONNECTED AHEAD OF TIMECLOCK CONTROL. NEC 700.12(F) |
| 2. PROVIDE SERVICE OUTLET FOR CU-1. NEC 210.63 |
| 3. PROVIDE SHOW WINDOW OUTLETS AND CIRCUIT WITH |
| LIGHTING CONTROL. NEC 210.62; FBC C405.2.3 |
| 4. LOAD CALCULATION IN PANEL SCHEDULE PROVIDED EXCEEDS |
| THE VALUE OF THE TRANSFORMER FEEDING THE UNIT. PROVIDE |
| CORRECTION. NEC 110.3 |
| 5. LOAD CALCULATION IN PANEL SCHEDULE PROVIDED SHOWS |
| THE SAME RATING FOR ALL REFRIGERATORS AND KITCHEN |
| EQUIPMENT. PROVIDE SPEC SHEETS WITH DETAILS OF LOAD FOR |
| EACH PIECE OF EQUIPMENT AND REVISE LOAD CALCULATION TO |
| REFLECT THE ACTUAL LOADS. NEC 110.3, 215.5, 220 |
| 6. PROVIDE DETAIL OF INTERIOR LIGHTING POWER |
| REQUIREMENTS IN RELATION TO THE CONNECTED INTERIOR |
| LIGHTING PROPOSED TO COMPLY WITH CODE. FBC C405.5 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |