Plan Review Notes
Plan Review Notes For Permit 17061005
Permit Number 17061005
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-05 08:51:47CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE NOTE FOR EXIT AND EMERGENCY LIGHTS TO BE
 CONNECTED AHEAD OF TIMECLOCK CONTROL. NEC 700.12(F)
 2. PROVIDE SERVICE OUTLET FOR CU-1. NEC 210.63
 3. PROVIDE SHOW WINDOW OUTLETS AND CIRCUIT WITH
 LIGHTING CONTROL. NEC 210.62; FBC C405.2.3
 4. LOAD CALCULATION IN PANEL SCHEDULE PROVIDED EXCEEDS
 THE VALUE OF THE TRANSFORMER FEEDING THE UNIT. PROVIDE
 CORRECTION. NEC 110.3
 5. LOAD CALCULATION IN PANEL SCHEDULE PROVIDED SHOWS
 THE SAME RATING FOR ALL REFRIGERATORS AND KITCHEN
 EQUIPMENT. PROVIDE SPEC SHEETS WITH DETAILS OF LOAD FOR
 EACH PIECE OF EQUIPMENT AND REVISE LOAD CALCULATION TO
 REFLECT THE ACTUAL LOADS. NEC 110.3, 215.5, 220
 6. PROVIDE DETAIL OF INTERIOR LIGHTING POWER
 REQUIREMENTS IN RELATION TO THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC C405.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  