2017-07-14 14:26:27FAILED
  
 PROVIDE WRITTEN RESPONSES.
  
 1) THE PROVIDED SITE PLAN SHOWS THE CURRENT PARKING LOT
 LAYOUT ADJACENT TO EXCHANGE COURT AND THE FPU METER IN
 WHAT IS NOW THE LANDSCAPE BUFFER. THIS BUFFER WILL BE
 REMOVED AS PART OF THE CONSTRUCTION OF THE NEW
 BENTLEY/ROLLS ROYCE BUILDING AND INSTEAD BECOME A DRIVE
 AISLE. ARE YOU PLANNING TO INSTALL THE GAS METER AND
 LINE AND THEN RELOCATE THEM WITHIN THE NEXT YEAR WHEN
 THE DRIVEWAY ENTRANCE IS REDONE? IT SEEMS LIKE A BETTER
 IDEA TO LOCATE THE METER AND LINE IN ITS FINAL LOCATION
 AND ONLY DO THE CONSTRUCTION ONE TIME.
  
 2) THE GAS METER IS NOT PERMITTED IN THE BUFFER WHERE
 IT WOULD ALLOW A GAP IN THE REQUIRED HEDGE. PROVIDE
 VERIFICATION THAT THE HEDGE IS NOT INTERRUPTED BY THE
 GAS METER IN WHICHEVER LOCATION IT ENDS UP.
  
 3) THE NEW GENERATOR REQUIRES SCREENING FOR THE FULL
 HEIGHT OF THE GENERATOR.
  
 4) PROVIDE THE GENERATOR DIMENSIONS ON THE PLAN, AS
 WELL AS THE DIMENSIONS FROM THE GENERATOR TO THE
 BUILDING, ELECTRICAL ROOM, ETC.
  