Plan Review Notes For Permit 17061002 |
Permit Number |
17061002 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-24 12:21:53 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. WINDOW REMOVAL IS NOT TYPICALLY PERMITTED WITHOUT A | | PERMIT TO RESTORE THE BUILDING TO A WATERTIGHT | | CONDITION. PLEASE ADDRESS BY DOING ONE OF THE FOLLOWING | | (FBC 107): | | | | REMOVE FROM SCOPE, OR | | REVISE PLAN TO INCLUDE MASONRY INFILL AND WINDOWS, OR | | VIA EMAIL, PROVIDE INFORMATION REGARDING RATIONALE AND | | TIME FRAME (THIS IS NOT PREFERABLE). | | | | 2. PLEASE HAVE THE ARCHITECT WHO IS WORKING ON THE PLAN | | CONTACT ME REGARDING EXITING STRATEGY. PER BUILDING | | OFFICIAL, DUE TO THE STAIRS WHICH ARE NOT REMOTELY | | LOCATED IN THIS EXISTING BUILDING (BUILT IN COMPLIANCE, | | LEVEL 3 ALTERATION, CHANGE OF OCCUPANCY TO A HIGHER | | HAZARD CATEGORY), TWO SMOKE DOORS (WITH HOLD OPEN) AND | | A SMOKE CONTROL SYSTEM WILL LIKELY BE REQUIRED. | | | | IT IS UNDERSTOOD THAT THIS WILL BE A PART OF THE | | BUILDING PERMIT, BUT RECOMMENDED TO HAVE THIS RESOLVED | | PRIOR TO PERMIT SUBMITTAL AS APPROVAL BY BUILDING | | OFFICIAL AND FIRE DEPT. WILL BE REQUIRED; FBC EB 805.2 | | (2), 1012.4.1(2). | | | | |
|