2017-10-17 10:27:503RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17060989
 10/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M2.1 & M6.1: PLEASE INCLUDE CU-19 AND AHU-19
 IN THE EQUIPMENT SCHEDULE, AND IN THE ENERGYGAUGE
 COMPLIANCE FORM.
  
 2) M3.1 & M6.1: INCLUDE PEFY-P18NMAU-E3 IN THE
 EQUIPMENT SCHEDULE, AND IN THE ENERGYGAUGE COMPLIANCE
 FORM.
  
 3) SUBMIT THE NOA FOR THE ROOF STAND WITH APPROVAL
 STAMP BY THE ENGINEER OF RECORD. PLEASE NOTE THE NOA
 NUMBER ON SHOWN IN THE EQUIPMENT MOUNTING DETAIL ON
 M7.1 IS ILLEGIBLE.
  