2017-09-29 16:51:442ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. 2ND REQUEST: PREVIOUS COMMENT #1A THE WATER CLOSET
 SHALL BE POSITIONED WITH A WALL OR PARTITION TO THE
 REAR AND TO ONE SIDE. PER FBC ACC 604.2
  
 2. 2ND REQUEST: PREVIOUS COMMENT #1C RESPONSE COMMENT
 INDICATES ON SHEET A3.0.1. DETAILS A, B, 7, 8, 9, 10,
 11 & 12 THE USE OF WINGITS GBW40 OR EQUAL. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.3: W.P.B. ADMINISTRATIVE CODE/2010 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" ?OR? ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION". THE
 PRODUCT HAS TO BE SPECIFIC.
  
 THE USE OF WINGITS GBW40 IS NOT BACKING AS REQUIRED FOR
 GRAB BARS. THIS IS NEW CONSTRUCTION, NEW WALLS, NOT A
 RETROFIT AS WHERE THIS PRODUCT WAS DESIGNED FOR
 INSTALLATION. TO USE THE WINGIT GBW40 TYPE OF
 INSTALLATION THE CONTRACTOR WILL HAVE TO NOT ONLY
 SUPPLY THE WINGIT GBW 40 ANCHOR BUT ALSO PROVIDE EACH
 OF THE GRAB BARS SINCE THE ANCHORS ARE TO ONLY USED
 WITH THE WINGIT GRAB BAR SYSTEM. THE ANCHORS WILL NEED
 TO BE INSTALLED AS REQUIRED FOR BACKING!!! PLEASE NOT
 THE ANCHORS WILL NEED TO BE INSTALLED SO THE SUPPORT
 GRAB BARS CAN SCREW DIRECTLY INTO THE ANCHOR. PLEASE
 PROVIDE ANCHOR INSTRUCTIONS IN THE NEXT PLAN REVIEW.
 THIS APPLICATION IS MORE IN LINE TO ALTERNATE MATERIALS
 AND METHODS. 104.11 ALTERNATE MATERIALS AND METHODS OF
 CONSTRUCTION.
  
 3. 2ND REQUEST: PREVIOUS COMMENT #1D A STANDARD ROLL-IN
 SHOWER SHALL HAVE A 30 INCH WIDE MINIMUM BY 60 INCH
 LONG MINIMUM CLEARANCE PROVIDED ADJACENT TO THE OPEN
 FACE OF THE SHOWER COMPARTMENT. PER FBC ACC 608.2.2.1
 A ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE
 36 INCHES EXACT WIDE AND 60 INCHES DEEP MINIMUM CLEAR
 INSIDE DIMENSIONS MEASURED AT CENTER POINTS OF OPPOSING
 SIDES. A 36 INCH WIDE MINIMUM ENTRY SHALL BE PROVIDED
 AT ONE END OF THE LONG SIDE OF THE COMPARTMENT.
  
 4. 2ND REQUEST: PREVIOUS COMMENT #1D IN ALL SHOWERS
 SHOWER SPRAY UNIT SHALL BE LOCATED ABOVE THE GRAB BAR,
 BUT NO HIGHER THAN 48 INCHES ABOVE THE SHOWER FLOOR.
 PER FBC ACC 608.5.2 /608.5.3/606.5.4
  
 5. 2ND REQUEST: PREVIOUS COMMENT #2 COMMON ACCESSIBLE
 BATHROOMS SHALL COMPLY WITH THE FOLLOWING SEC PER FBC
 ACC
 2C, 2D IN ALL SHOWERS SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES ABOVE THE SHOWER FLOOR. PER FBC ACC 608.5.2
 /608.5.3/606.5.4
  
  
 6. 2ND REQUEST: PREVIOUS COMMENT #7. IN BATHROOMS 229 +
 230 THE BRANCH DRAIN FOR THE HWC + HLAV + UR + HDF
 SHOULD BE A CIRCUIT VENT AND THE STACK FOR THE HLAV
 SHALL CONNECT BETWEEN THE TWO MOST UPSTREAM FIXTURES
 WHICH WOULD BE THE 2 HWC. PER FBC PL 914.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  