Date |
Text |
2017-09-29 16:51:44 | 2ND REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. 2ND REQUEST: PREVIOUS COMMENT #1A THE WATER CLOSET |
| SHALL BE POSITIONED WITH A WALL OR PARTITION TO THE |
| REAR AND TO ONE SIDE. PER FBC ACC 604.2 |
| |
| 2. 2ND REQUEST: PREVIOUS COMMENT #1C RESPONSE COMMENT |
| INDICATES ON SHEET A3.0.1. DETAILS A, B, 7, 8, 9, 10, |
| 11 & 12 THE USE OF WINGITS GBW40 OR EQUAL. 2014 FLORIDA |
| BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| 107.2.1.3: W.P.B. ADMINISTRATIVE CODE/2010 DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| IN PART, NOR THE TERM "LEGAL" ?OR? ITS EQUIVALENT BE |
| USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION". THE |
| PRODUCT HAS TO BE SPECIFIC. |
| |
| THE USE OF WINGITS GBW40 IS NOT BACKING AS REQUIRED FOR |
| GRAB BARS. THIS IS NEW CONSTRUCTION, NEW WALLS, NOT A |
| RETROFIT AS WHERE THIS PRODUCT WAS DESIGNED FOR |
| INSTALLATION. TO USE THE WINGIT GBW40 TYPE OF |
| INSTALLATION THE CONTRACTOR WILL HAVE TO NOT ONLY |
| SUPPLY THE WINGIT GBW 40 ANCHOR BUT ALSO PROVIDE EACH |
| OF THE GRAB BARS SINCE THE ANCHORS ARE TO ONLY USED |
| WITH THE WINGIT GRAB BAR SYSTEM. THE ANCHORS WILL NEED |
| TO BE INSTALLED AS REQUIRED FOR BACKING!!! PLEASE NOT |
| THE ANCHORS WILL NEED TO BE INSTALLED SO THE SUPPORT |
| GRAB BARS CAN SCREW DIRECTLY INTO THE ANCHOR. PLEASE |
| PROVIDE ANCHOR INSTRUCTIONS IN THE NEXT PLAN REVIEW. |
| THIS APPLICATION IS MORE IN LINE TO ALTERNATE MATERIALS |
| AND METHODS. 104.11 ALTERNATE MATERIALS AND METHODS OF |
| CONSTRUCTION. |
| |
| 3. 2ND REQUEST: PREVIOUS COMMENT #1D A STANDARD ROLL-IN |
| SHOWER SHALL HAVE A 30 INCH WIDE MINIMUM BY 60 INCH |
| LONG MINIMUM CLEARANCE PROVIDED ADJACENT TO THE OPEN |
| FACE OF THE SHOWER COMPARTMENT. PER FBC ACC 608.2.2.1 |
| A ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE |
| 36 INCHES EXACT WIDE AND 60 INCHES DEEP MINIMUM CLEAR |
| INSIDE DIMENSIONS MEASURED AT CENTER POINTS OF OPPOSING |
| SIDES. A 36 INCH WIDE MINIMUM ENTRY SHALL BE PROVIDED |
| AT ONE END OF THE LONG SIDE OF THE COMPARTMENT. |
| |
| 4. 2ND REQUEST: PREVIOUS COMMENT #1D IN ALL SHOWERS |
| SHOWER SPRAY UNIT SHALL BE LOCATED ABOVE THE GRAB BAR, |
| BUT NO HIGHER THAN 48 INCHES ABOVE THE SHOWER FLOOR. |
| PER FBC ACC 608.5.2 /608.5.3/606.5.4 |
| |
| 5. 2ND REQUEST: PREVIOUS COMMENT #2 COMMON ACCESSIBLE |
| BATHROOMS SHALL COMPLY WITH THE FOLLOWING SEC PER FBC |
| ACC |
| 2C, 2D IN ALL SHOWERS SHOWER SPRAY UNIT SHALL BE |
| LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48 |
| INCHES ABOVE THE SHOWER FLOOR. PER FBC ACC 608.5.2 |
| /608.5.3/606.5.4 |
| |
| |
| 6. 2ND REQUEST: PREVIOUS COMMENT #7. IN BATHROOMS 229 + |
| 230 THE BRANCH DRAIN FOR THE HWC + HLAV + UR + HDF |
| SHOULD BE A CIRCUIT VENT AND THE STACK FOR THE HLAV |
| SHALL CONNECT BETWEEN THE TWO MOST UPSTREAM FIXTURES |
| WHICH WOULD BE THE 2 HWC. PER FBC PL 914.2 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |