Plan Review Notes For Permit 17060989 |
Permit Number |
17060989 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-09-20 16:02:13 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17060989 | | 9/20/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE REQUESTED ENGINEERING FOR INSTALLATION OF THE | | EXTERIOR CONDENSERS WAS NOT SUBMITTED- PLEASE COMPLY | | AND PROVIDE A MECHANICAL ROOF PLAN SHOWING THE | | LOCATIONS OF THE UNITS- SECTION 107.2.1 WPB AMENDMENTS | | TO THE FBC. | | | | 2) SHEET M3.1 APPEARS TO HAVE BEEN OVERLAYED BY M2.1 | | MAKING IT ILLEGIBLE IN MANY AREAS- PLEASE CORRECT- | | SECTION 107.2.1.4 WPB AMENDMENTS TO THE FBC. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|