2017-09-13 16:52:30 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17060989 |
| ADD: 101 N. CLEMATIS ST. SUITE: 200 |
| CONT: BSA CORP. |
| TEL: 561-272-6350 / KIM UNKE |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: WED. SEPT. 13/ 2017 |
| ACTION: DENIED |
| |
| 1-2) COMPLIED. |
| |
| 3) SHEET A1.1.1: |
| |
| 3A) COMPLIED. DOORS 202 & 216. |
| |
| 3B) RESPONSE COMMENT INDICATES ON SHEET A3.0.1. DETAILS |
| A, B, 7, 8, 9, 10, 11 & 12 THE USE OF WINGITS GBW40 OR |
| EQUAL. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION 107.2.1.3: W.P.B. ADMINISTRATIVE |
| CODE/2010 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" ?OR? |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". THE PRODUCT HAS TO BE SPECIFIC. |
| |
| THE USE OF WINGITS GBW40 IS NOT BACKING AS REQUIRED FOR |
| GRAB BARS. THIS IS NEW CONSTRUCTION, NEW WALLS, NOT A |
| RETROFIT AS WHERE THIS PRODUCT WAS DESIGNED FOR |
| INSTALLATION. TO USE THE WINGIT GBW40 TYPE OF |
| INSTALLATION THE CONTRACTOR WILL HAVE TO NOT ONLY |
| SUPPLY THE WINGIT GBW 40 ANCHOR BUT ALSO PROVIDE EACH |
| OF THE GRAB BARS SINCE THE ANCHORS ARE TO ONLY USED |
| WITH THE WINGIT GRAB BAR SYSTEM. THE ANCHORS WILL NEED |
| TO BE INSTALLED AS REQUIRED FOR BACKING!!! PLEASE NOT |
| THE ANCHORS WILL NEED TO BE INSTALLED SO THE SUPPORT |
| GRAB BARS CAN SCREW DIRECTLY INTO THE ANCHOR. PLEASE |
| PROVIDE ANCHOR INSTRUCTIONS IN THE NEXT PLAN REVIEW. |
| THIS APPLICATION IS MORE IN LINE TO ALTERNATE MATERIALS |
| AND METHODS. 104.11 ALTERNATE MATERIALS AND METHODS OF |
| CONSTRUCTION. |
| |
| THE 2014 ACCESSIBILITY CODE 609.8 STRUCTURAL STRENGTH, |
| ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS |
| USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS |
| IS APPLIED AT ANY POINT ON THE GRAB BAR, FASTENER, |
| MOUNTING DEVICE, OR SUPPORTING STRUCTURE. |
| |
| |
| |
| 1ST ROUND OF COMMENTS. PRIVATE RESTROOMS 215 AND 225 |
| ARE TO BE CONSIDERED ADAPTABLE THE PLANS WILL NEED TO |
| SHOW COMPLIANCE WITH THE ACCESSIBILITY CODE 604.5 GRAB |
| BARS EXCEPTION # 1. GRAB BARS SHALL NOT BE REQUIRED TO |
| BE INSTALLED IN A TOILET ROOM FOR A SINGLE OCCUPANT |
| ACCESSED ONLY THROUGH A PRIVATE OFFICE AND NOT FOR |
| COMMON USE OR PUBLIC USE PROVIDED THAT REINFORCEMENT |
| HAS BEEN INSTALLED IN WALLS AND LOCATED SO AS TO PERMIT |
| THE INSTALLATION OF GRAB BARS COMPLYING WITH 604.5. |
| ACCESSIBILITY CODE 609.4 POSITION OF GRAB BARS. 609.8 |
| STRUCTURAL STRENGTH. |
| ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS |
| USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS |
| IS APPLIED AT ANY POINT ON THE GRAB BAR, FASTENER, |
| MOUNTING DEVICE, OR SUPPORTING STRUCTURE. |
| |
| 3C)SEMI- COMPLIED. PRIVATE RESTROOMS 215 AND 225 SIZE / |
| CLEARANCE AROUND THE WATER CLOSET, 60 INCHES) & |
| 604.3.2.(OVERLAP). |
| |
| 3D-G) COMPLIED. |
| |
| 4) SHEET A1.1.3: |
| 4A) COMPLIED. |
| |
| 4B)SEMI-COMPLIED. FLOOR FINISHES, WD-1 MADISON SLATE |
| WHITE OAK WILL THERE BE A FLOOR UNDERLAYMENT, CRACK |
| SUPPRESSANT, INSTALLED BEFORE TILE INSTALLATION IF SO |
| THEN COMPLIANCE WITH FLAME SPREAD- FBC-B 2014 603.1. |
| EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| MORE THAN 200. |
| |
| POR-1 PORCELAIN TILE FLOOR WILL THERE BE A FLOOR |
| UNDERLAYMENT, CRACK SUPPRESSANT, INSTALLED BEFORE TILE |
| INSTALLATION IF SO THEN COMPLIANCE WITH FLAME SPREAD- |
| FBC-B 2014 603.1. EXCEPTION 2. INSULATION INSTALLED |
| BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT |
| INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME |
| SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 1ST ROUND OF COMMENTS. FLOOR FINISHES ARE NOT GIVEN. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA, |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| INTERIOR FINISHES FLOOR FINISHES & TRIM MISSING (FLAME |
| SPREAD/SMOKE DEVELOPMENT). |
| |
| 5) COMPLIED. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |