2017-09-13 16:52:302014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060989
 ADD: 101 N. CLEMATIS ST. SUITE: 200
 CONT: BSA CORP.
 TEL: 561-272-6350 / KIM UNKE
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. SEPT. 13/ 2017
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) SHEET A1.1.1:
  
 3A) COMPLIED. DOORS 202 & 216.
  
 3B) RESPONSE COMMENT INDICATES ON SHEET A3.0.1. DETAILS
 A, B, 7, 8, 9, 10, 11 & 12 THE USE OF WINGITS GBW40 OR
 EQUAL. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1.3: W.P.B. ADMINISTRATIVE
 CODE/2010 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" ?OR?
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". THE PRODUCT HAS TO BE SPECIFIC.
  
 THE USE OF WINGITS GBW40 IS NOT BACKING AS REQUIRED FOR
 GRAB BARS. THIS IS NEW CONSTRUCTION, NEW WALLS, NOT A
 RETROFIT AS WHERE THIS PRODUCT WAS DESIGNED FOR
 INSTALLATION. TO USE THE WINGIT GBW40 TYPE OF
 INSTALLATION THE CONTRACTOR WILL HAVE TO NOT ONLY
 SUPPLY THE WINGIT GBW 40 ANCHOR BUT ALSO PROVIDE EACH
 OF THE GRAB BARS SINCE THE ANCHORS ARE TO ONLY USED
 WITH THE WINGIT GRAB BAR SYSTEM. THE ANCHORS WILL NEED
 TO BE INSTALLED AS REQUIRED FOR BACKING!!! PLEASE NOT
 THE ANCHORS WILL NEED TO BE INSTALLED SO THE SUPPORT
 GRAB BARS CAN SCREW DIRECTLY INTO THE ANCHOR. PLEASE
 PROVIDE ANCHOR INSTRUCTIONS IN THE NEXT PLAN REVIEW.
 THIS APPLICATION IS MORE IN LINE TO ALTERNATE MATERIALS
 AND METHODS. 104.11 ALTERNATE MATERIALS AND METHODS OF
 CONSTRUCTION.
  
 THE 2014 ACCESSIBILITY CODE 609.8 STRUCTURAL STRENGTH,
 ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS
 USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS
 IS APPLIED AT ANY POINT ON THE GRAB BAR, FASTENER,
 MOUNTING DEVICE, OR SUPPORTING STRUCTURE.
  
  
  
 1ST ROUND OF COMMENTS. PRIVATE RESTROOMS 215 AND 225
 ARE TO BE CONSIDERED ADAPTABLE THE PLANS WILL NEED TO
 SHOW COMPLIANCE WITH THE ACCESSIBILITY CODE 604.5 GRAB
 BARS EXCEPTION # 1. GRAB BARS SHALL NOT BE REQUIRED TO
 BE INSTALLED IN A TOILET ROOM FOR A SINGLE OCCUPANT
 ACCESSED ONLY THROUGH A PRIVATE OFFICE AND NOT FOR
 COMMON USE OR PUBLIC USE PROVIDED THAT REINFORCEMENT
 HAS BEEN INSTALLED IN WALLS AND LOCATED SO AS TO PERMIT
 THE INSTALLATION OF GRAB BARS COMPLYING WITH 604.5.
 ACCESSIBILITY CODE 609.4 POSITION OF GRAB BARS. 609.8
 STRUCTURAL STRENGTH.
 ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS
 USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS
 IS APPLIED AT ANY POINT ON THE GRAB BAR, FASTENER,
 MOUNTING DEVICE, OR SUPPORTING STRUCTURE.
  
 3C)SEMI- COMPLIED. PRIVATE RESTROOMS 215 AND 225 SIZE /
 CLEARANCE AROUND THE WATER CLOSET, 60 INCHES) &
 604.3.2.(OVERLAP).
  
 3D-G) COMPLIED.
  
 4) SHEET A1.1.3:
 4A) COMPLIED.
  
 4B)SEMI-COMPLIED. FLOOR FINISHES, WD-1 MADISON SLATE
 WHITE OAK WILL THERE BE A FLOOR UNDERLAYMENT, CRACK
 SUPPRESSANT, INSTALLED BEFORE TILE INSTALLATION IF SO
 THEN COMPLIANCE WITH FLAME SPREAD- FBC-B 2014 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 POR-1 PORCELAIN TILE FLOOR WILL THERE BE A FLOOR
 UNDERLAYMENT, CRACK SUPPRESSANT, INSTALLED BEFORE TILE
 INSTALLATION IF SO THEN COMPLIANCE WITH FLAME SPREAD-
 FBC-B 2014 603.1. EXCEPTION 2. INSULATION INSTALLED
 BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 1ST ROUND OF COMMENTS. FLOOR FINISHES ARE NOT GIVEN.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA,
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES FLOOR FINISHES & TRIM MISSING (FLAME
 SPREAD/SMOKE DEVELOPMENT).
  
 5) COMPLIED.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved