2017-07-20 13:05:351ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SINGLE USER BATHROOMS 215 AND 225 ACCESSED
 THROUGH THE PRIVATE OFFICES SHALL COMPLY WITH THE
 FOLLOWING SEC OF THE FBC ACC
  
 A) 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION.
  
 B) 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 C) THE GRAB BARS DON NEED TO BE INSTALLED BUT THE
 BACKING FOR THE GRAB BARS SHALL BE INSTALLED. 604.5
 GRAB BARS.
 GRAB BARS FOR WATER CLOSETS SHALL COMPLY WITH 609. GRAB
 BARS SHALL BE PROVIDED ON THE SIDE WALL CLOSEST TO THE
 WATER CLOSET AND ON THE REAR WALL.
 EXCEPTIONS:
 1. GRAB BARS SHALL NOT BE REQUIRED TO BE INSTALLED IN A
 TOILET ROOM FOR A SINGLE OCCUPANT ACCESSED ONLY THROUGH
 A PRIVATE OFFICE AND NOT FOR COMMON USE OR PUBLIC USE
 PROVIDED THAT REINFORCEMENT HAS BEEN INSTALLED IN WALLS
 AND LOCATED SO AS TO PERMIT THE INSTALLATION OF GRAB
 BARS COMPLYING WITH 604.5.
 THIS INCLUDES THE SHOWERS
  
 D) THE DIMENSIONS OF THE SHOWER SHALL COMPLY WITH ONE
 OF THESE CODE SEC.
 1)608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES
 (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS
 MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND
 SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE
 FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES
 (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG
 MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE
 PROVIDED.
 2) 608.2.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 30
 INCHES (760 MM) WIDE MINIMUM BY 60 INCHES (1525 MM)
 DEEP MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER
 POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES
 (1525 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT.
 3) 608.2.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS.
 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 36
 INCHES (915 MM) WIDE AND 60 INCHES (1525 MM) DEEP
 MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER
 POINTS OF OPPOSING SIDES. A 36 INCH (915 MM) WIDE
 MINIMUM ENTRY SHALL BE PROVIDED AT ONE END OF THE LONG
 SIDE OF THE COMPARTMENT.
  
 E) THE LOCATION OF THE SHOWER CONTROLS SHALL COMPLY
 WITH ONE OF THE FOLLOWING CODE SEC.
 1)608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
 2) 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT
 IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY
 UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO
 THE SEAT WALL AND SHALL BE LOCATED 27 INCHES (685 MM)
 MAXIMUM FROM THE SEAT WALL
 3) 608.5.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT
 IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY
 UNIT SHALL BE LOCATED ON THE SIDE WALL ADJACENT TO THE
 SEAT 27 INCHES (685 MM) MAXIMUM FROM THE SIDE WALL
 BEHIND THE SEAT OR SHALL BE LOCATED ON THE BACK WALL
 OPPOSITE THE SEAT 15 INCHES (380 MM) MAXIMUM, LEFT OR
 RIGHT, OF THE CENTERLINE OF THE SEAT. WHERE A SEAT IS
 NOT PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY
 UNIT SHALL BE INSTALLED ON THE SIDE WALL FARTHEST FROM
 THE COMPARTMENT ENTRY.
  
 2. COMMON ACCESSIBLE BATHROOMS SHALL COMPLY WITH THE
 FOLLOWING SEC PER FBC ACC
  
 A) 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 B) SHT. A3.02 DETAIL #3 THE GRAB BAR SHALL BE MEASURED
 TO THE TOP OF THE GRIPPING SURFACE PER 609.4
  
 C) 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT
 IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY
 UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO
 THE SEAT WALL AND SHALL BE LOCATED 27 INCHES (685 MM)
 MAXIMUM FROM THE SEAT WALL.
  
 D) 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
  
 E) 602 DRINKING FOUNTAINS
 602.1 GENERAL.
 DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602.
  
 F) PROVIDE THE DIMENSION OF THE DEPTH OF THE TRANSFER
 SHOWER 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES
 (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS
 MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND
 SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE
 FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES
 (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG
 MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE
 PROVIDED.
  
 3. THE BREAKROOM 206 SINK SHALL COMPLY WITH FBC ACC
 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4. THE HORIZONTAL DRY VENT AT THE END OF THE BRANCH
 DRAIN FOR THE HSH IN TH COMMON BATHROOMS AND THE
 HORIZONTAL DRY VENT AT THE END OF THE BRANCH DRAIN FOR
 THE BATHROOMS 214 AND 213 ARE NOT PERMITTED. PER FBC PL
 905.3 VENT CONNECTION TO DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
 905.4 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
  
 5. THE BRANCH VENT FOR THE HSH AND WC IN BATHROOMS 229
 + 230 SHALL CONNECT ABOVE THE CENTER LINE OF THE
 HORIZONTAL DRAIN BETWEEN THE HSH AND WC PER FBC PL
 914.2
  
 6. ON THE BRANCH DRAIN FOR BATHROOMS 214 + 213 A DRY
 VENT SHALL CONNECT BETWEEN THE LAV STACK AND WC OR
 BETWEEN THE 2 WC. PER FBC PL 914.2 OR 912.1 AND 908.1
  
 7. IN BATHROOMS 229 + 230 THE BRANCH DRAIN FOR THE HWC
 + HLAV + UR + HDF SHOULD BE A CIRCUIT VENT AND THE
 STACK FOR THE HLAV SHALL CONNECT BETWEEN THE TWO MOST
 UPSTREAM FIXTURES WHICH WOULD BE THE 2 HWC. PER FBC PL
 914.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  