2017-07-19 09:29:381ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060989
 7/19/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PER THE SUBMITTED AC CALCULATIONS, THE TRANE FCCB12
 MODELS ARE OVERSIZED FOR SYSTEMS FCC-4, 11, & 13-
 SECTION C403.2.2 FBC-14 ENERGY CONSERVATION.
  
 2) SHEET M2.1: IT APPEARS FIRE DAMPERS ARE MISSING FOR
 THE O/A DUCTS PENETRATING THE SHAFT AND TENANT
 SEPARATION WALLS- SECTION 607.5.2.
  
 3) M2.1: IT APPEARS AHU-1 IS MISLABELED AS AHU-2.
  
 4) M2.1: SHOW THE LOCATIONS OF ACCESS PANELS FOR THE
 FAN COIL UNITS LOCATED ABOVE HARD CEILINGS. PLEASE
 INCLUDE DIMENSIONS AND CONSTRUCTION DETAILS- SECTION
 306.1
  
 5) M2.1: PROVIDE THE FLEX DUCT SIZES ON THE PLAN.
  
 6) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE ROOF TOP CHILLER- SECTION 301.15.
  
 7) SUBMIT A COMMISSIONING PLAN IN COMPLIANCE WITH
 SECTION C408.2 & C408.2.1 FBC-14 ENERGY CONSERVATION.
  