2017-07-19 09:29:38 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17060989 | | 7/19/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PER THE SUBMITTED AC CALCULATIONS, THE TRANE FCCB12 | | MODELS ARE OVERSIZED FOR SYSTEMS FCC-4, 11, & 13- | | SECTION C403.2.2 FBC-14 ENERGY CONSERVATION. | | | | 2) SHEET M2.1: IT APPEARS FIRE DAMPERS ARE MISSING FOR | | THE O/A DUCTS PENETRATING THE SHAFT AND TENANT | | SEPARATION WALLS- SECTION 607.5.2. | | | | 3) M2.1: IT APPEARS AHU-1 IS MISLABELED AS AHU-2. | | | | 4) M2.1: SHOW THE LOCATIONS OF ACCESS PANELS FOR THE | | FAN COIL UNITS LOCATED ABOVE HARD CEILINGS. PLEASE | | INCLUDE DIMENSIONS AND CONSTRUCTION DETAILS- SECTION | | 306.1 | | | | 5) M2.1: PROVIDE THE FLEX DUCT SIZES ON THE PLAN. | | | | 6) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF | | THE ROOF TOP CHILLER- SECTION 301.15. | | | | 7) SUBMIT A COMMISSIONING PLAN IN COMPLIANCE WITH | | SECTION C408.2 & C408.2.1 FBC-14 ENERGY CONSERVATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|