2017-07-20 15:15:45 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: |
| |
| 1. CIRCUIT HA-8 AND HA-10 DO NOT SHOW AS BEING |
| CONTROLLED FROM THE LUTRON LIGHTING CONTROL PANEL. |
| WHILE THERE ARE SOME AREAS FOR THE CIRCUITS THAT HAVE |
| VACANCY SENSORS, IT APPEARS THAT SOME AREAS DO NOT HAVE |
| THE PROPER AUTOMATIC CONTROL. PLEASE CLARIFY AND/OR |
| CORRECT. FBC 405.2.2, FBC 107.2.1 |
| 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2 |
| AND ASHREA 90.1: 8.4.2 |
| 3. PROVIDE GFCI PROTECTED OUTLET AND SWITCH CONTROLLED |
| LIGHT FOR SERVICING EACH FCU LOCATED IN HARD CEILING. |
| FBC MECHANICAL CODE M306.3.1 |
| 4. THE LOAD FOR PANEL LA IS NOT INCLUDED IN THE LOAD |
| CALCULATION FOR PANEL HA. PROVIDE ACCURATE LOAD |
| CALCULATION TO CONFIRM SERVICE EQUIPMENT IS ADEQUATELY |
| SIZED. NEC 220, 408.30 |
| 5. BREAKER FOR EWH APPEARS TO BE TOO BIG FOR THE LOAD. |
| PANEL SCHEDULE STATES THIS IS A 3.2 KW LOAD, A 30 AMP |
| BREAKER IS NOT THE CORRECT SIZE. PROVIDE CORRECTION. |
| NEC 422.13, 422.11 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |