2017-07-20 15:15:45CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. CIRCUIT HA-8 AND HA-10 DO NOT SHOW AS BEING
 CONTROLLED FROM THE LUTRON LIGHTING CONTROL PANEL.
 WHILE THERE ARE SOME AREAS FOR THE CIRCUITS THAT HAVE
 VACANCY SENSORS, IT APPEARS THAT SOME AREAS DO NOT HAVE
 THE PROPER AUTOMATIC CONTROL. PLEASE CLARIFY AND/OR
 CORRECT. FBC 405.2.2, FBC 107.2.1
 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2
 AND ASHREA 90.1: 8.4.2
 3. PROVIDE GFCI PROTECTED OUTLET AND SWITCH CONTROLLED
 LIGHT FOR SERVICING EACH FCU LOCATED IN HARD CEILING.
 FBC MECHANICAL CODE M306.3.1
 4. THE LOAD FOR PANEL LA IS NOT INCLUDED IN THE LOAD
 CALCULATION FOR PANEL HA. PROVIDE ACCURATE LOAD
 CALCULATION TO CONFIRM SERVICE EQUIPMENT IS ADEQUATELY
 SIZED. NEC 220, 408.30
 5. BREAKER FOR EWH APPEARS TO BE TOO BIG FOR THE LOAD.
 PANEL SCHEDULE STATES THIS IS A 3.2 KW LOAD, A 30 AMP
 BREAKER IS NOT THE CORRECT SIZE. PROVIDE CORRECTION.
 NEC 422.13, 422.11
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  