Date |
Text |
2017-07-13 12:13:42 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17060989 |
| ADD: 101 N. CLEMATIS ST. SUITE: 200 |
| CONT: BSA CORP. |
| TEL: 561-272-6350 / KIM UNKE |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. JULY 13/ 2017 |
| ACTION: DENIED |
| |
| 1) SHEET A0.1.1. NOTE NUMBER 31 MAKES REFERENCE TO THE |
| CITY OF MIAMI FIRE DEPARTMENT REGULATIONS. PLEASE |
| UPDATE PLANS TO THE WEST PALM BEACH FIRE DEPARTMENT |
| REGULATIONS. 107.2.1.3. ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 2) SHEET ALS1.1 107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| (3) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE 503). |
| |
| 3) SHEET A1.1.1: |
| 3A) DOORS 202 & 216 ARE BOTH POCKET DOORS SHEET A2.01 |
| DOOR SCHEDULE AND HARDWARE GROUP LABELED # 9. |
| THE HARDWARE GROUP WILL NEED TO SHOW COMPLIANCE |
| WITH2014 FBC-ACCESSIBILITY CODE 404.2.7 DOOR AND GATE |
| HARDWARE. WHERE SLIDING DOORS ARE IN THE FULLY OPEN |
| POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND |
| USABLE FROM BOTH SIDES. |
| ADVISORY 404.2.7 DOOR AND GATE HARDWARE. DOOR HARDWARE |
| THAT CAN BE OPERATED WITH A CLOSED FIST OR A LOOSE GRIP |
| ACCOMMODATES THE GREATEST RANGE OF USERS. HARDWARE THAT |
| REQUIRES SIMULTANEOUS HAND AND FINGER MOVEMENTS REQUIRE |
| GREATER DEXTERITY AND COORDINATION, AND IS NOT |
| RECOMMENDED. |
| |
| 3B) PRIVATE RESTROOMS 215 AND 225 ARE TO BE CONSIDERED |
| ADAPTABLE THE PLANS WILL NEED TO SHOW COMPLIANCE WITH |
| THE ACCESSIBILITY CODE 604.5 GRAB BARS EXCEPTION # 1. |
| GRAB BARS SHALL NOT BE REQUIRED TO BE INSTALLED IN A |
| TOILET ROOM FOR A SINGLE OCCUPANT ACCESSED ONLY THROUGH |
| A PRIVATE OFFICE AND NOT FOR COMMON USE OR PUBLIC USE |
| PROVIDED THAT REINFORCEMENT HAS BEEN INSTALLED IN WALLS |
| AND LOCATED SO AS TO PERMIT THE INSTALLATION OF GRAB |
| BARS COMPLYING WITH 604.5. |
| ACCESSIBILITY CODE 609.4 POSITION OF GRAB BARS. 609.8 |
| STRUCTURAL STRENGTH. |
| ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS |
| USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS |
| IS APPLIED AT ANY POINT ON THE GRAB BAR, FASTENER, |
| MOUNTING DEVICE, OR SUPPORTING STRUCTURE. |
| |
| 3C) PRIVATE RESTROOMS 215 AND 225 ARE TO BE CONSIDERED |
| ADAPTABLE THE PLANS WILL NEED TO SHOW COMPLIANCE WITH |
| THE ACCESSIBILITY CODE 604.3.1 (SIZE / CLEARANCE AROUND |
| THE WATER CLOSET, 60 INCHES) & 604.3.2.(OVERLAP). WITH |
| THE BATHROOMS BEING REQUIRED TO BE ADAPTABLE THE |
| FIXTURE LAYOUT WILL NEED TO AND WASTE LINES WILL NEED |
| TO BE INSTALLED AS IF AN ACCESSIBLE BATHROOM, TO BE |
| CONSIDERED ADAPTABLE. FOR CHAPTER 6 FOR EACH CODE |
| REQUIREMENT IF THERE IS AN EXCEPTION FOR PRIVATE |
| BATHROOMS OR RESTROOMS THERE IS AN EXCEPTION STATING AS |
| SUCH, NONE GIVEN FOR EITHER OF THE ABOVE CODE SECTIONS, |
| MAKING THE LAYOUT OF FIXTURES WITH CLEARANCES A |
| REQUIREMENT, BACKING A REQUIREMENT AND FIXTURE LOCATION |
| A REQUIREMENT, TO MAKE THE UNIT AN ADAPTABLE UNIT. |
| |
| 3D) PRIVATE RESTROOMS 215 AND 225 ARE TO BE CONSIDERED |
| ADAPTABLE THE PLANS WILL NEED TO SHOW COMPLIANCE WITH |
| THE ACCESSIBILITY CODE FOR A STANDARD ROLL-IN TYPE |
| SHOWER COMPARTMENT. |
| AGAIN FOR A ADAPTABLE SHOWER THE PLANS WILL NEED TO |
| SHOW WHERE THE BACKING WILL BE PLACED FOR POSSIBLE |
| FUTURE GRAB BARS INCOMPLIANCE WITH ACCESS. CODE 608.3 |
| EXCEPTION # 1. |
| |
| 3E) PLEASE INDICATE HOW COMPLIANCE WITH EITHER 608.3.2 |
| STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS OR 608.3.3 |
| ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS WILL BE |
| ACHIEVED. |
| |
| 3F) PLEASE PROVIDE COMPLIANCE WITH THE SHOWER: |
| 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS. IN |
| STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE |
| CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE |
| LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48 |
| INCHES ABOVE THE SHOWER FLOOR. WHERE A SEAT IS |
| PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT |
| SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO THE |
| SEAT WALL AND SHALL BE LOCATED 27 INCHES MAXIMUM FROM |
| THE SEAT WALL. |
| |
| OR |
| |
| 608.5.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS. |
| CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE |
| LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48 |
| INCHES ABOVE THE SHOWER FLOOR. WHERE A SEAT IS |
| PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT |
| SHALL BE LOCATED ON THE SIDE WALL ADJACENT TO THE SEAT |
| 27 INCHES MAXIMUM FROM THE SIDE WALL BEHIND THE SEAT OR |
| SHALL BE LOCATED ON THE BACK WALL OPPOSITE THE SEAT 15 |
| INCHES MAXIMUM, LEFT OR RIGHT, OF THE CENTERLINE OF THE |
| SEAT. WHERE A SEAT IS NOT PROVIDED, THE CONTROLS, |
| FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON |
| THE SIDE WALL FARTHEST FROM THE COMPARTMENT ENTRY. |
| |
| 3G) 2014 ACCESSIBILITY CODE 608.7 THRESHOLDS. |
| THRESHOLDS IN ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE |
| 1/2 INCH (13 MM) HIGH MAXIMUM IN ACCORDANCE WITH 303. |
| IN TRANSFER TYPE SHOWER COMPARTMENTS, THRESHOLDS 1/2 |
| INCH (13 MM) HIGH MAXIMUM SHALL BE BEVELED, ROUNDED, OR |
| VERTICAL. |
| |
| 4) SHEET A1.1.3: |
| 4A) SUSTAINABLE NOTE WALL COVERING LIST COMPLIANCE WITH |
| THE 2007/2009 SUPPLEMENTS SECTION |
| 803. PLEASE UPDATE CODE DATA TO THE CURRENT 2014 FBC-B. |
| |
| 4B) FLOOR FINISHES ARE NOT GIVEN. 2014 FLORIDA BUILDING |
| CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.5 |
| MINIMUM PLAN REVIEW CRITERIA, |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| INTERIOR FINISHES FLOOR FINISHES & TRIM MISSING (FLAME |
| SPREAD/SMOKE DEVELOPMENT). |
| |
| 5) SHEET A2.01 DOOR AND WINDOW TYPES SHOW VARIOUS |
| SECTIONS THROUGH THE FRAME AND GLAZING, SECTIONS 2-11, |
| MISSING THESE SECTIONS NOT FOUND ON THIS SHEET. |
| 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |