2017-07-06 11:08:281ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060985
 7/6/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1: NO VENTILATION NOTES ARE SHOWN AT
 APARTMENTS B & G. PLEASE INDICATE HOW THESE APARTMENTS
 ARE BEING VENTILATED AND PROVIDE CALCULATIONS FOR ALL
 OF THE APARTMENTS SHOWN IN THE PLANS- SECTION 401.2.
  
 2) M1.1: THE CHASE FOR THE DRYER MAKEUP AIR DUCT (NOTE
 #7) IS NOT SHOWN ON THE ARCHITECTURAL PLAN SHEET A-103.
 CLARIFY IF THIS IS A RATED CHASE AND PROVIDE A FIRE
 DAMPER FOR THE DUCT PENETRATION IF APPLICABLE- SECTION
 607.5.5.
  
 3) M1.1: PROVIDE DETAILS FOR THE ROOFTOP DUCT: A) DUCT
 MATERIAL B) INSULATION TYPE, THICKNESS AND R-VALUE.
  
 4) M1.1: PROVIDE AN ENLARGED DETAIL OF THE ROOFTOP DUCT
 SUPPORTS INDICATING DUCT SUPPORT MATERIALS, ANCHORING
 TO ROOF STRUCTURE, SPACING OF SUPPOTS, AND CONNECTIONS
 TO DUCTWORK- SECTION 301.15.
  
 5) REFER TO BUILDING REVIEW COMMENTS FOR WIND LOAD
 ENGINEERING COMPLIANCE FOR THE ROOF TOP CONDENSERS.
  
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 DRYERS- SECTION 504.1.
  
 7) ENERGY FORM R405-2014: A) ALL FORMS REQUIRE THE
 OWNER'S SIGNATURE AND DATES- SEE PAGE 1. B) THE FORMS
 SUBMITTED FOR APTS. A- G AND THE CORRIDOR SHOW COOLING
 CAPACITIES FOR THE SYSTEMS THAT DON'T MATCH THE
 CAPACITIES LISTED IN THE SCHEDULE ON M0.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER