2017-07-06 11:08:28 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #17060985 |
| 7/6/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M1.1: NO VENTILATION NOTES ARE SHOWN AT |
| APARTMENTS B & G. PLEASE INDICATE HOW THESE APARTMENTS |
| ARE BEING VENTILATED AND PROVIDE CALCULATIONS FOR ALL |
| OF THE APARTMENTS SHOWN IN THE PLANS- SECTION 401.2. |
| |
| 2) M1.1: THE CHASE FOR THE DRYER MAKEUP AIR DUCT (NOTE |
| #7) IS NOT SHOWN ON THE ARCHITECTURAL PLAN SHEET A-103. |
| CLARIFY IF THIS IS A RATED CHASE AND PROVIDE A FIRE |
| DAMPER FOR THE DUCT PENETRATION IF APPLICABLE- SECTION |
| 607.5.5. |
| |
| 3) M1.1: PROVIDE DETAILS FOR THE ROOFTOP DUCT: A) DUCT |
| MATERIAL B) INSULATION TYPE, THICKNESS AND R-VALUE. |
| |
| 4) M1.1: PROVIDE AN ENLARGED DETAIL OF THE ROOFTOP DUCT |
| SUPPORTS INDICATING DUCT SUPPORT MATERIALS, ANCHORING |
| TO ROOF STRUCTURE, SPACING OF SUPPOTS, AND CONNECTIONS |
| TO DUCTWORK- SECTION 301.15. |
| |
| 5) REFER TO BUILDING REVIEW COMMENTS FOR WIND LOAD |
| ENGINEERING COMPLIANCE FOR THE ROOF TOP CONDENSERS. |
| |
| 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| DRYERS- SECTION 504.1. |
| |
| 7) ENERGY FORM R405-2014: A) ALL FORMS REQUIRE THE |
| OWNER'S SIGNATURE AND DATES- SEE PAGE 1. B) THE FORMS |
| SUBMITTED FOR APTS. A- G AND THE CORRIDOR SHOW COOLING |
| CAPACITIES FOR THE SYSTEMS THAT DON'T MATCH THE |
| CAPACITIES LISTED IN THE SCHEDULE ON M0.2. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |