Plan Review Notes
Plan Review Notes For Permit 17060985
Permit Number 17060985
Review Stop B
Sequence Number 1
Notes
Date Text
2017-06-28 15:11:432014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17060985
 W. P. B. PERMIT: 16070183
 ADD: 518 S. DIXIE HWY.
 CONT: ECONSTRUCTION LLC
 TEL: 954-570-9500
 E-MAIL: BRIAN @ TBBG.NET
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 28/ 2017
 ACTION: DENIED
  
 1) THIS REVISION IS FOR ADDING APPROXIMATELY 1375 SQ.
 FT. THE DOLLAR AMOUNT OF THE INCREASE FOR THIS REVISION
 IS GIVEN AS $60,000.00 IN VALUE. THIS WORKS OUT TO BE
 $43.63 A SQUARE FOOT. THE ICC TABLES PUT A R2
 OCCUPANCY/ BUILDING TYPE VB AT $104.47 A SQUARE FOOT.
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) SHEET A-101 THE SITE PLAN HAS A NOTATION THAT THE
 EXISTING TAYLOR SHOP HAS NO WORK IN THE ADJACENT UNIT.
 PLEASE NOTE TO THE EAST OF THIS BUILDING A EGRESS COURT
 ( EXIT DISCHARGE FROM THE EXTERIOR DINING GARDEN) IS
 BEING CREATED ACCESS TO THE PUBLIC WAY. WHEN YOU VIEW
 THIS PROPERTY USING GOOGLE THERE IS A A/C CONDENSING
 UNIT THAT IS NOT SHOWN IN THE EGRESS COURT. THIS UNIT
 WILL NEED TO BE MOVED TO GAIN ACCESS FROM THE EXTERIOR
 DINING AREA. 2014 FBC-B 1027.4.1 EGRESS COURT WIDTHS.
  
 3) BOTH SHEETS A-101 & A-103 BOTH SHOW A WALL TYPE/
 CHASE G THE SAME PROBLEM WITH WALL TYPE H. PLEASE
 PROVIDE THE COMPLETE WALL DESIGN TYPE, NOT JUST UL 404,
 UL 404 I COULD NOT FIND ANY REFERENCE TO A 1 HOUR FIRE
 RATED SHEAR WALL. 2014 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.3: W.P.B. ADMINISTRATIVE CODE. DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES, WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH
 THE TECHNICAL CODES.
  
 4) BOTH SHEETS A-101 & A-103 SHOW AN OPENING SCHEDULE:
  
 4A) WINDOW OPENING TYPE NUMBER 8 WAS RED LINES TO GET
 THE PERMIT ISSUED WITH A 49X48 INCH HORIZONTAL SLIDER.
 THE PLANS ARE NOT MARKED THIS TO BE A REVISION BUT THE
 NEW REVISION INDICATES A 3-6X3-4 SINGLE CASEMENT
 WINDOW, PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION
 FOR THE CLEAR OPENING FOR THIS TYPE WINDOW. PLEASE NOTE
 THE PRODUCT APPROVAL SUBMITTED ES WINDOWS, SERIES 5000
 OUTSWING ALUMINUM CASEMENT- L. M. I. NOA 15-0129.05.
  
 4B) OPENING # 11 IS NOW INDICATED TO BE A 2 FT. -10
 INCH WIDE DOOR. THIS IS A REVISION FROM THE ISSUED SET
 OF PLANS THAT IS NOT MARKED WITH A CLOUD OR DELTA.
 PLEASE REVIEW THE 2014 FBC-B 1008.1.1. SIZE OF
 DOORS. THE CLEAR OPENINGS OF DOORWAYS WITH SWINGING
 DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR
 AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. THE 2012
 IBC COMMENTARY STATES FOR A 34 INCH DOOR WITH THE DOOR
 THICKNESS (1 ? INCHES) AND THE DOOR STOP ON THE
 OPPOSITE SIDE THERE IS NOT A CLEAR 32 INCHES. IN
 SECTION 1008.1.1.1 PROJECTIONS INTO THE CLEAR OPENING
 THE CODE STATES WHAT CAN BE DEDUCTED FOR CLEARANCE INTO
 THE CLEAR OPENING. FAIR HOUSING ALLOWS FOR THE
 CLEARANCE OF THE DOOR STOP FOR EGRESS REQUIREMENTS THE
 CODE DOES NOT. PLEASE NOTE IF THE DESIGNER INTENDS TO
 USE OFF-SET HINGES PLEASE INDICATE AS SUCH AND PROVIDE
 MANUFACTURES SPECIFICATION HOW MUCH THIS TYPE HINGE
 WILL THROUGH THE DOOR FOR CLEAR WIDTH?
  
 5) SHEET A-105:
  
 5A) SHOWS THE EXHAUST DUCT UP THROUGH THE 2NS STORY
 ROOF. ON THE ISSUED SET OF PLANS THE MECHANICAL SHEET
 M.1.1 NOTE 13 INDICATED THAT THE FUTURE KITCHEN EXHAUST
 IS TO BE UNDER A SEPARATE PERMIT. TO DATE THERE HAS
 BEEN NO PRODUCT APPROVALS SUBMITTED FOR A ROOF TOP CURB
 NOR ANY STRUCTURAL DETAILS FOR THE FRAMING AROUND THE
 VOID WHERE THE EXHAUST DUCT WILL PENETRATE THE ROOF
 DECK.
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 5B) SHOWS THE ROOF TOP A/C STAND LOCATIONS, A
 MIAMI-DADE NOA 16-0601.01 WAS SUBMITTED, IT HAS NOT
 BEEN REVIEWED BY THE DESIGNER OF RECORD BEFORE BEING
 SUBMITTED TO THE BUILDING DEPARTMENT. FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 5C) THE ROOF TOP A/C STAND PRODUCT APPROVAL A
 MIAMI-DADE NOA # 16-0601.01 WAS SUBMITTED, NOT REVIEWED
 BY THE DESIGNER OF RECORD. NEITHER THE CONTRACTOR NOR
 THE DESIGNER OF RECORD HAVE FOLLOWED THE PRODUCT
 APPROVAL IN CALCULATING THE AREA OF THE ROOF TOP
 COMPRESSORS, THE MEAN ROOF HEIGHT OF THE STAND AND
 COMPRESSORS, WEIGHT, CIRCLED THE DESIGN PARAMETERS IN
 THE TABLES, ANCHORS AND UPLIFT VERSES MOMENT. IDENTIFY
 EACH OF THE ABOVE REQUIREMENTS TO DETERMINE CODE
 COMPLIANCE.
  
 6) THE LIFE SAFETY PLAN A-107;
 6A) DOES NOT INDICATE COMPLIANCE WITH FBC-B 907.2.11.2
 GROUPS R-2. SINGLE- OR MULTIPLE-STATION SMOKE ALARMS
 SHALL BE INSTALLED AND MAINTAINED IN GROUPS
 R-2REGARDLESS OF OCCUPANT LOAD AT ALL OF THE FOLLOWING
 LOCATIONS:
  
 1. ON THE CEILING OR WALL OUTSIDE OF EACH SEPARATE
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF BEDROOMS.
 2. IN EACH ROOM USED FOR SLEEPING PURPOSES.
  
 6B) THIS PERMIT DOES NOT INDICATE IF GAS APPLIANCES
 WILL BE ON THE 1ST FLOOR IN THE KITCHEN AREA. IF THERE
 IS GOING TO BE ANY GAS APPLIANCES WITHIN THE BUILDING,
 THEN COMPLIANCE WITH 2014 FBC-B SECTION [F] 908.7
 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUELBURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES IN THE NEW BUILDING OR
 ADDITION, OR AT SUCH OTHER LOCATIONS AS REQUIRED BY
 THIS CODE.
 908.7.1 CARBON MONOXIDE ALARM.
 THE REQUIREMENTS OF SECTION 908.7 SHALL BE SATISFIED BY
 PROVIDING FOR ONE OF THE FOLLOWING ALARM INSTALLATIONS:
 1. A HARD-WIRED CARBON MONOXIDE ALARM.
 2. A BATTERY-POWERED CARBON MONOXIDE ALARM.
 3. A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE
 ALARM.
 4. A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND
 SMOKE ALARM.
 908.7.2 COMBINATION ALARMS. COMBINATION SMOKE/CARBON
 MONOXIDE ALARMS SHALL BE LISTED AND LABELED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY.
  
 7) SHEET A-201 AND A-202 NOW SHOW WHAT APPEARS TO BE
 METAL AWNINGS (FIRST FLOOR) AND AWNING TYPE PROJECTIONS
 ON THE 2ND FLOOR OF THE SOUTH AND WEST ELEVATIONS.
 PLEASE BE AWARE AWNINGS REQUIRE A SEPARATE PERMIT, FEES
 AND ASSOCIATED FEES. PLEASE ALSO BE AWARE THE PLANS DO
 NOT SHOW WHERE THE PROPERTY LINE IS IN RELATION TO THE
 AWNINGS, CODE COMPLIANCE CANNOT BE ACHIEVED. TYPE OF
 FRAME AND FINISH MATERIAL IS NOT PROVIDE NOR WIND
 DESIGN.
 2014 FBC-B 3202.3.1 AWNINGS, CANOPIES, MARQUEES AND
 SIGNS. AWNINGS, CANOPIES, MARQUEES AND SIGNS SHALL BE
 CONSTRUCTED SO AS TO SUPPORT APPLICABLE LOADS AS
 SPECIFIED IN CHAPTER 16. AWNINGS, CANOPIES, MARQUEES
 AND SIGNS WITH LESS THAN 15 FEET (4572 MM) CLEARANCE
 ABOVE THE SIDEWALK SHALL NOT EXTEND INTO OR OCCUPY MORE
 THAN TWO-THIRDS THE WIDTH OF THE SIDEWALK MEASURED FROM
 THE BUILDING. STANCHIONS OR COLUMNS THAT SUPPORT
 AWNINGS, CANOPIES, MARQUEES AND SIGNS SHALL BE LOCATED
 NOT LESS THAN 2 FEET (610 MM) IN FROM THE CURB LINE.
  
 8) SHEET S-104 THE WINDOW LOCATED IN THE END WALL ZONE
 # 5 THE PRESSURES ARE LOW FOR THIS ZONE. ZONE 5 FOR 10
 SQ. FT. EXPOSURE B UP TO 30 FEET ELEVATION, -41.9/ 132
 MPH/ VASD. 1609.1.2.3.1/ 1609.1.5.
  
 9) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT