2017-06-28 15:11:43 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17060985 |
| W. P. B. PERMIT: 16070183 |
| ADD: 518 S. DIXIE HWY. |
| CONT: ECONSTRUCTION LLC |
| TEL: 954-570-9500 |
| E-MAIL: BRIAN @ TBBG.NET |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JUNE 28/ 2017 |
| ACTION: DENIED |
| |
| 1) THIS REVISION IS FOR ADDING APPROXIMATELY 1375 SQ. |
| FT. THE DOLLAR AMOUNT OF THE INCREASE FOR THIS REVISION |
| IS GIVEN AS $60,000.00 IN VALUE. THIS WORKS OUT TO BE |
| $43.63 A SQUARE FOOT. THE ICC TABLES PUT A R2 |
| OCCUPANCY/ BUILDING TYPE VB AT $104.47 A SQUARE FOOT. |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2) SHEET A-101 THE SITE PLAN HAS A NOTATION THAT THE |
| EXISTING TAYLOR SHOP HAS NO WORK IN THE ADJACENT UNIT. |
| PLEASE NOTE TO THE EAST OF THIS BUILDING A EGRESS COURT |
| ( EXIT DISCHARGE FROM THE EXTERIOR DINING GARDEN) IS |
| BEING CREATED ACCESS TO THE PUBLIC WAY. WHEN YOU VIEW |
| THIS PROPERTY USING GOOGLE THERE IS A A/C CONDENSING |
| UNIT THAT IS NOT SHOWN IN THE EGRESS COURT. THIS UNIT |
| WILL NEED TO BE MOVED TO GAIN ACCESS FROM THE EXTERIOR |
| DINING AREA. 2014 FBC-B 1027.4.1 EGRESS COURT WIDTHS. |
| |
| 3) BOTH SHEETS A-101 & A-103 BOTH SHOW A WALL TYPE/ |
| CHASE G THE SAME PROBLEM WITH WALL TYPE H. PLEASE |
| PROVIDE THE COMPLETE WALL DESIGN TYPE, NOT JUST UL 404, |
| UL 404 I COULD NOT FIND ANY REFERENCE TO A 1 HOUR FIRE |
| RATED SHEAR WALL. 2014 WEST PALM BEACH AMENDMENTS TO |
| THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| 107.2.1.3: W.P.B. ADMINISTRATIVE CODE. DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES, WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH |
| THE TECHNICAL CODES. |
| |
| 4) BOTH SHEETS A-101 & A-103 SHOW AN OPENING SCHEDULE: |
| |
| 4A) WINDOW OPENING TYPE NUMBER 8 WAS RED LINES TO GET |
| THE PERMIT ISSUED WITH A 49X48 INCH HORIZONTAL SLIDER. |
| THE PLANS ARE NOT MARKED THIS TO BE A REVISION BUT THE |
| NEW REVISION INDICATES A 3-6X3-4 SINGLE CASEMENT |
| WINDOW, PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION |
| FOR THE CLEAR OPENING FOR THIS TYPE WINDOW. PLEASE NOTE |
| THE PRODUCT APPROVAL SUBMITTED ES WINDOWS, SERIES 5000 |
| OUTSWING ALUMINUM CASEMENT- L. M. I. NOA 15-0129.05. |
| |
| 4B) OPENING # 11 IS NOW INDICATED TO BE A 2 FT. -10 |
| INCH WIDE DOOR. THIS IS A REVISION FROM THE ISSUED SET |
| OF PLANS THAT IS NOT MARKED WITH A CLOUD OR DELTA. |
| PLEASE REVIEW THE 2014 FBC-B 1008.1.1. SIZE OF |
| DOORS. THE CLEAR OPENINGS OF DOORWAYS WITH SWINGING |
| DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR |
| AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. THE 2012 |
| IBC COMMENTARY STATES FOR A 34 INCH DOOR WITH THE DOOR |
| THICKNESS (1 ? INCHES) AND THE DOOR STOP ON THE |
| OPPOSITE SIDE THERE IS NOT A CLEAR 32 INCHES. IN |
| SECTION 1008.1.1.1 PROJECTIONS INTO THE CLEAR OPENING |
| THE CODE STATES WHAT CAN BE DEDUCTED FOR CLEARANCE INTO |
| THE CLEAR OPENING. FAIR HOUSING ALLOWS FOR THE |
| CLEARANCE OF THE DOOR STOP FOR EGRESS REQUIREMENTS THE |
| CODE DOES NOT. PLEASE NOTE IF THE DESIGNER INTENDS TO |
| USE OFF-SET HINGES PLEASE INDICATE AS SUCH AND PROVIDE |
| MANUFACTURES SPECIFICATION HOW MUCH THIS TYPE HINGE |
| WILL THROUGH THE DOOR FOR CLEAR WIDTH? |
| |
| 5) SHEET A-105: |
| |
| 5A) SHOWS THE EXHAUST DUCT UP THROUGH THE 2NS STORY |
| ROOF. ON THE ISSUED SET OF PLANS THE MECHANICAL SHEET |
| M.1.1 NOTE 13 INDICATED THAT THE FUTURE KITCHEN EXHAUST |
| IS TO BE UNDER A SEPARATE PERMIT. TO DATE THERE HAS |
| BEEN NO PRODUCT APPROVALS SUBMITTED FOR A ROOF TOP CURB |
| NOR ANY STRUCTURAL DETAILS FOR THE FRAMING AROUND THE |
| VOID WHERE THE EXHAUST DUCT WILL PENETRATE THE ROOF |
| DECK. |
| FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, |
| DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| |
| 5B) SHOWS THE ROOF TOP A/C STAND LOCATIONS, A |
| MIAMI-DADE NOA 16-0601.01 WAS SUBMITTED, IT HAS NOT |
| BEEN REVIEWED BY THE DESIGNER OF RECORD BEFORE BEING |
| SUBMITTED TO THE BUILDING DEPARTMENT. FBC 107.3.4.1 |
| PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED |
| BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 5C) THE ROOF TOP A/C STAND PRODUCT APPROVAL A |
| MIAMI-DADE NOA # 16-0601.01 WAS SUBMITTED, NOT REVIEWED |
| BY THE DESIGNER OF RECORD. NEITHER THE CONTRACTOR NOR |
| THE DESIGNER OF RECORD HAVE FOLLOWED THE PRODUCT |
| APPROVAL IN CALCULATING THE AREA OF THE ROOF TOP |
| COMPRESSORS, THE MEAN ROOF HEIGHT OF THE STAND AND |
| COMPRESSORS, WEIGHT, CIRCLED THE DESIGN PARAMETERS IN |
| THE TABLES, ANCHORS AND UPLIFT VERSES MOMENT. IDENTIFY |
| EACH OF THE ABOVE REQUIREMENTS TO DETERMINE CODE |
| COMPLIANCE. |
| |
| 6) THE LIFE SAFETY PLAN A-107; |
| 6A) DOES NOT INDICATE COMPLIANCE WITH FBC-B 907.2.11.2 |
| GROUPS R-2. SINGLE- OR MULTIPLE-STATION SMOKE ALARMS |
| SHALL BE INSTALLED AND MAINTAINED IN GROUPS |
| R-2REGARDLESS OF OCCUPANT LOAD AT ALL OF THE FOLLOWING |
| LOCATIONS: |
| |
| 1. ON THE CEILING OR WALL OUTSIDE OF EACH SEPARATE |
| SLEEPING AREA IN THE IMMEDIATE VICINITY OF BEDROOMS. |
| 2. IN EACH ROOM USED FOR SLEEPING PURPOSES. |
| |
| 6B) THIS PERMIT DOES NOT INDICATE IF GAS APPLIANCES |
| WILL BE ON THE 1ST FLOOR IN THE KITCHEN AREA. IF THERE |
| IS GOING TO BE ANY GAS APPLIANCES WITHIN THE BUILDING, |
| THEN COMPLIANCE WITH 2014 FBC-B SECTION [F] 908.7 |
| CARBON MONOXIDE PROTECTION. |
| EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| ISSUED AND HAVING A FOSSIL-FUELBURNING HEATER OR |
| APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| ROOM USED FOR SLEEPING PURPOSES IN THE NEW BUILDING OR |
| ADDITION, OR AT SUCH OTHER LOCATIONS AS REQUIRED BY |
| THIS CODE. |
| 908.7.1 CARBON MONOXIDE ALARM. |
| THE REQUIREMENTS OF SECTION 908.7 SHALL BE SATISFIED BY |
| PROVIDING FOR ONE OF THE FOLLOWING ALARM INSTALLATIONS: |
| 1. A HARD-WIRED CARBON MONOXIDE ALARM. |
| 2. A BATTERY-POWERED CARBON MONOXIDE ALARM. |
| 3. A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE |
| ALARM. |
| 4. A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND |
| SMOKE ALARM. |
| 908.7.2 COMBINATION ALARMS. COMBINATION SMOKE/CARBON |
| MONOXIDE ALARMS SHALL BE LISTED AND LABELED BY A |
| NATIONALLY RECOGNIZED TESTING LABORATORY. |
| |
| 7) SHEET A-201 AND A-202 NOW SHOW WHAT APPEARS TO BE |
| METAL AWNINGS (FIRST FLOOR) AND AWNING TYPE PROJECTIONS |
| ON THE 2ND FLOOR OF THE SOUTH AND WEST ELEVATIONS. |
| PLEASE BE AWARE AWNINGS REQUIRE A SEPARATE PERMIT, FEES |
| AND ASSOCIATED FEES. PLEASE ALSO BE AWARE THE PLANS DO |
| NOT SHOW WHERE THE PROPERTY LINE IS IN RELATION TO THE |
| AWNINGS, CODE COMPLIANCE CANNOT BE ACHIEVED. TYPE OF |
| FRAME AND FINISH MATERIAL IS NOT PROVIDE NOR WIND |
| DESIGN. |
| 2014 FBC-B 3202.3.1 AWNINGS, CANOPIES, MARQUEES AND |
| SIGNS. AWNINGS, CANOPIES, MARQUEES AND SIGNS SHALL BE |
| CONSTRUCTED SO AS TO SUPPORT APPLICABLE LOADS AS |
| SPECIFIED IN CHAPTER 16. AWNINGS, CANOPIES, MARQUEES |
| AND SIGNS WITH LESS THAN 15 FEET (4572 MM) CLEARANCE |
| ABOVE THE SIDEWALK SHALL NOT EXTEND INTO OR OCCUPY MORE |
| THAN TWO-THIRDS THE WIDTH OF THE SIDEWALK MEASURED FROM |
| THE BUILDING. STANCHIONS OR COLUMNS THAT SUPPORT |
| AWNINGS, CANOPIES, MARQUEES AND SIGNS SHALL BE LOCATED |
| NOT LESS THAN 2 FEET (610 MM) IN FROM THE CURB LINE. |
| |
| 8) SHEET S-104 THE WINDOW LOCATED IN THE END WALL ZONE |
| # 5 THE PRESSURES ARE LOW FOR THIS ZONE. ZONE 5 FOR 10 |
| SQ. FT. EXPOSURE B UP TO 30 FEET ELEVATION, -41.9/ 132 |
| MPH/ VASD. 1609.1.2.3.1/ 1609.1.5. |
| |
| 9) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |