Plan Review Notes
Plan Review Notes For Permit 17060979
Permit Number 17060979
Review Stop P
Sequence Number 1
Notes
Date Text
2017-07-19 09:33:101ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.3.1 TRANSFER
 TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES FROM THE CONTROL WALL.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.5.1 TRANSFER
 TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 610.3 SHOWER
 COMPARTMENT SEATS. IN TRANSFER-TYPE SHOWERS, THE SEAT
 SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN 3
 INCHES (75 MM) OF THE COMPARTMENT ENTRY. THE TOP OF THE
 SEAT SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM ABOVE THE BATHROOM FINISH FLOOR. SEATS
 SHALL COMPLY WITH 610.3.1 OR 610.3.2.
  
 4. TEMPERATURE LIMITING DEVISES FOR TEMPERED WATER
 DELIVERED FROM LAVATORY'S SHALL CONFORM TO ASSE 1070 OR
 CSA B125.3 PER FBC PL 416.5 , THE LEONARD TM-26-LL AND
 THE EEMAX EX48TFS SPECKED OUT ON THE PLAN DO NOT COMPLY
 WITH ASSE 1070 PER MANUFACTURE SPECIFICATIONS.
  
 5. THE BRANCH DRAIN FOR THE EWC SHALL CONNECT DOWN
 STREAM OF THE BATHROOM GROUP . PER FBC PL 912.1
  
 6. THE SANITARY AND VENT FOR THE FLOOR DRAIN IN ROOM
 301 APPEARS TO BE CONNECTING IN TO A EXISTING OA DUCT
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 7. A SERVICE SINK IS REQUIRED IS THERE AN EXITING ONE
 PLEASE SHOW ON THE PLAN. PER FBC PL TABLE 403.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  