Notes |
Date |
Text |
2017-07-18 08:54:16 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17060979 | | 7/18/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M2.01: INDICATE HOW O/A IS BEING PROVIDED TO | | THE CORRIDOR AND AHU-3-1A. | | | | 2) M2.02: INDICATE HOW O/A IS BEING SUPPLIED TO THE | | RECEPTION, BREAKROOM, AND LOUNGE AREAS AND AHU'S 3-1E, | | 3-1F-2, 3-1H-1, & 3-1H-2. | | | | 3) M2.02: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR | | CU-3-1A/B TO VERIFY THE UNITS CAN BE INSTALLED INSIDE | | THE INTERIOR SPACE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|