Plan Review Notes
Plan Review Notes For Permit 17060979
Permit Number 17060979
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-20 07:58:01CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT
 NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA,
 WIRELESS SYSTEMS, KITCHEN HOODS ETC. A NOTE WILL
 SUFFICE. WPB AMENDMENTS TO FBC 107.3.5
 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2
 AND ASHREA 90.1: 8.4.2
 3. ALL RECEPTACLES IN KITCHEN AREAS (ROOM 311) REQUIRE
 GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8(B)(2)
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL IN THE NEW LOCATION TO CONFIRM THE STATED AIC
 RATING OF THE PANELS IS ADEQUATE. NEC 110.9, 110.10
 5. DATA/PHONE ROOM 315 DOES NOT SHOW ANY POWER OUTLETS.
 HOW WILL THE EQUIPMENT IN THIS ROOM GET POWER? PLEASE
 CLARIFY AND/OR CORRECT. FBC 107.2.1
 6. PROVIDE GRAPH OF INTERIOR LIGHTING POWER ALLOWANCES
 PER THE FBC ENERGY CODE IN RELATION TO THE CONNECTED
 INTERIOR LIGHTING PROPOSED TO COMPLY WITH CODE. FBC
 C405.5, 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  