2017-07-11 14:06:141ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PUT A NOTE ON THE PLAN THAT A SEPARATE PERMIT
 IS REQUIRED FOR THE BACKFLOW. PER WPB AMEND TO FBC
 107.2.1
  
 2. SHT P2.1 DETAIL #6 THE BACK FLOW IS REQUIRED TO BE
 LEAD FREE THE WATTS MODEL #909 THAT YOU REFERENCE ON
 DETAIL IS NOT LEAD FREE MANUFACTURE SPECS SHOWING
 DEVICE IS LEAD FREE WILL BE REQUIRED WITH SEPARATE
 PERMIT APPLICATION SO THIS DETAIL DOES NOT NEED TO BE
 ON THE MASTER SET OF PLANS. PER FBC RES P2905.2.1
  
 3. PLEASE SHOW WATER HEATER PAN DRAIN TERMINATION/ PER
 FBC RES P2801.5.2
  
 4. SHOW T AND P VALVE DISCHARGE PIPING. TO COMPLY WITH
 FBC RES P2803.6.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  