Plan Review Notes
Plan Review Notes For Permit 17060927
Permit Number 17060927
Review Stop M
Sequence Number 1
Notes
Date Text
2017-07-19 13:36:13PLAN DENIED
 1) CAN'T HAVE RETURN AIR IN KITCHEN. REFER TO
 SECTION M1602.2 PROHIBITED SOURCES #4
 2014 RESIDENTIAL CODE
 2) MASTER BEDROOM REFER TO SECTION M1602.4
 BALANCED RETURN AIR 2014 RESIDENTIAL CODE
 3) HEAT LODE REQUIRED, REFER TO SECTION M1401.3
 SIZING 2014 RESIDENTIAL CODE.
  