Plan Review Notes For Permit 17060927 |
Permit Number |
17060927 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-19 13:36:13 | PLAN DENIED | | 1) CAN'T HAVE RETURN AIR IN KITCHEN. REFER TO | | SECTION M1602.2 PROHIBITED SOURCES #4 | | 2014 RESIDENTIAL CODE | | 2) MASTER BEDROOM REFER TO SECTION M1602.4 | | BALANCED RETURN AIR 2014 RESIDENTIAL CODE | | 3) HEAT LODE REQUIRED, REFER TO SECTION M1401.3 | | SIZING 2014 RESIDENTIAL CODE. | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|