Plan Review Notes
Plan Review Notes For Permit 17060918
Permit Number 17060918
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-21 16:51:01CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO REVISE PERMIT #16090649 TO SHOW NEW CONNECTION
 FOR THE SOLAR PHOTOVOLTAIC SYSTEM
 PLANS SHO 40A BREAKERS FOR SYSTEM ON RISER, E-4 SHOWS
 90A TO MDP?
  
 NEED TO REVISE PERMIT #16080934 TO SHOW FIRE ALARM
 CONNECTION TO FIRE PUMP, FLOWS AND TAMPERS
  
 RISER SHOWS CONNECTION TO A FIRE PUMP, PLEASE SEE
 SECTION 695 OF THE NEC FOR CONNECTION OF A FIRE PUMP
 SYSTEM.
 WIRING IS TO BE SEPARATE FROM ALL OTHER WIRING.
 SHOW HOW WIRE TO FIRE PUMP IS TO BE KEPT SEPARASTE FROM
 ALL OTHER WIRING
  
 SUBMIT PANEL SCHEDULES FOR MDP SHOWINF NEW
 PHOTOVOLTALIC SYSTEM 90A SINGLE PHASE , THREE PHASE?
  
 PLEASE SHOW WHICH PERMIT HAS THE FIREPUMP INSTALLATION
 ON IT?
 WHICH PERMIT #
  
  