Plan Review Notes
Plan Review Notes For Permit 17060851
Permit Number 17060851
Review Stop M
Sequence Number 2
Notes
Date Text
2017-08-17 15:32:48NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR AGREES TO SUBMIT REQUIRED
 INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE
 INSPECTION TO AVOID CONFLICTS/DELAYS. REVISION FEES
 WILL APPLY. CONTRACTOR TO ADVICE IN WRITING IF PROVISO
 OPTION IS PREFERRED AT THIS TIME.
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS NOT
 JUST THE SUMMARY SHEET. CALCULATIONS TO BE DONE BASED
 ON THE ACTUAL ORIENTATION OF THE BUILDING AS REQUIRED
 BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE: REPEAT COMMENT. PROVIDE COMPLETE PACKAGE.
 NEED TO VERIFY WITH REVISED ENERGY CALCULATIONS. SEE
 BUILDING REVIEW FOR COMMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER CLEARLY SPECIFYING
 HOW EACH COMMENT IS ADDRESSED TO EXPEDITE THE REVIEW
 PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  