Plan Review Notes
Plan Review Notes For Permit 17060851
Permit Number 17060851
Review Stop B
Sequence Number 2
Notes
Date Text
2017-08-17 10:40:39NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR AGREES TO SUBMIT REQUIRED
 INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE
 INSPECTION TO AVOID CONFLICTS/DELAYS. REVISION FEES
 WILL APPLY. CONTRACTOR TO ADVICE IN WRITING IF PROVISO
 OPTION IS PREFERRED AT THIS TIME.
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) ENERGY CALCULATIONS NEED TO BE DONE FOR THE ACTUAL
 ORIENTATION OF THE BUILDING NOT WORST CASE. REVISE ITEM
 #5 AS REQUIRED BY SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
 RESPONSE. REPEAT COMMENT. FRONT PAGE SAYS NO WORST
 CASE. NEVERTHELESS, SECOND PAGE SAYS ROTATED 315
 DEGREES AND ORIENTATION SHOWN ON FOLLOWING PAGES IS NOT
 THE ACTUAL ORIENTATION OF THE BUILDING. REVISE AS
 REQUIRED. PROVIDE CALCULATIONS FOR THE ACTUAL
 ORIENTATION OF THE BUILDING.
  
 B) REVISE WALL TYPE ON ITEM #9(B) FOR THE ADJACENT
 WALL. PLANS CALL FOR METAL FRAMING ON ONE SIDE AND WOOD
 FRAMING ON THE OTHER SIDE. SEC. 101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
 RESPONSE: PLANS AND ENERGY CALCULATIONS NEED TO BE
 COORDINATED. FLOOR PLAN AND GENERAL WALL LEGEND ON
 SHEET 2.1 SPECIFY WOOD FRAMING FOR THE BEARING WALLS L
 AND METAL STUDS FOR NON BEARING WALLS. PLANS AND ENERGY
 CALCULATIONS NEED TO MATCH. REVISE AS REQUIRED.
  
 C) HEATING INFORMATION SHOWN ON ITEM #13 DOESN'T T
 MATCH INFORMATION SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT.
  
 D) CONTRACTOR TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD AS REQUIRED BY SEC. R405.4.3
 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT.
  
 E) REVISE WALLS AND WINDOWS ORIENTATION SHOWN ON PAGE 3
 OF 5. COORDINATE WITH ITEM #1(A) ABOVE. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT.
  
 F) REVISE THE DOORS INFORMATION SHOWN ON PAGE 3 OF 5.
 WHERE ARE THE 16'-0" X 8'-0" INSULATED DOORS?. SEE
 PLANS AND PRODUCT APPROVALS SUBMITTED. NOTE: DOORS WITH
 GLAZING NEED TO BE CONSIDERED IN THE WINDOWS AREA AS
 REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY CONSERVATION.
 REVISE AS REQUIRED.
 RESPONSE: REPEAT COMMENT.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON ITEM #7 IS REQUIRED WHEN THE
 ENERGY CALCULATIONS ARE NOT USING THE SOFTWARE DEFAULT
 FACTOR.
  
 2- ROOF TILE UNDERLAYMENT FL11288-R15 SUBMITTED:
 CLEARLY MARK SPECIFIC UNDERLAYMENT INSTALLATION SHOWING
 THE DESIGN PRESSURES OF PROPOSED INSTALLATION TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: SEE PAGES 5,6 AND 7 OF
 EVALUATION REPORT SUBMITTED. MARK SPECIFIC APPLICATION
 #.
 RESPONSE: REPEAT COMMENT. CLEARLY IDENTIFY WHICH
 ASSEMBLY ON PAGE 5, 6 OR 7 IS GOING TO BE INSTALLED.
 NOTE: MAKE SURE ASSEMBLY IS FOR WOOD DECK. IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES, THEN IT CAN NOT BE USED.
 (NOTE: ON 08/22/17 ROOFING CONTRACTOR E-MAILED FRSA
 TABLES SHOWING PROPOSED UNDERLAYMENT INSTALLATION).
  
 3- TRUSS PACKAGE SUBMITTED:
 A) DESIGN LOADS DON'T MATCH DESIGN CRITERIA SPECIFIED
 BY THE ENGINEER OF RECORD. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT. TRUSS ENGINEER TO SEE DESIGN
 CRITERIA ON SHEET 2.1 AND REVISE AS REQUIRED.
  
 B) BASED ON ITEM #3(A) ABOVE REVISED TRUSS PACKAGE TO
 BE REVIEWED AND APPROVED IN WRITING BY THE ENGINEER OF
 RECORD PRIOR TO SUBMITTAL T THIS OFFICE. SEC. 107.3.4.2
 CITY AMENDMENTS.
  
 C) TRUSS LAYOUT AND ALL INDIVIDUAL TRUSS DRAWINGS NEED
 TO BE SIGNED AND SEALED AND HAVE THE TRUSS ENGINEER
 INFORMATION IN ALL DRAWINGS AS REQUIRED BY FAC
 61G15-31.003.
 RESPONSE: REPEAT COMMENT.
  
 ****PLEASE PROVIDE RESPONSE LETTER CLEARLY SPECIFYING
 HOW EACH COMMENT IS ADDRESSED TO EXPEDITE THE REVIEW
 PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712