2017-07-19 16:20:18 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS NOT |
| JUST THE SUMMARY SHEET. CALCULATIONS TO BE DONE BASED |
| ON THE ACTUAL ORIENTATION OF THE BUILDING AS REQUIRED |
| BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| 2- EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE MISSING |
| EQUIPMENT INFORMATION. SPECIFY THE COIL MODEL AND THE |
| AHRI REFERENCE NUMBER. ALSO, PROVIDE THE MANUFACTURER |
| AND MODEL INFORMATION ABOUT THE HEATING EQUIPMENT. SEC. |
| R403.6.1 FBC-ENERGY CONSERVATION. |
| |
| 3- A/C PLAN TO SHOW ALL THE EQUIPMENT INFORMATION. |
| COORDINATE WITH ITEM #2 ABOVE. SEC. 107.3.5.3(10) CITY |
| AMENDMENTS. |
| |
| 4- A/C PLAN TO HAVE THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 5- CONDENSING UNIT MOUNTING DETAIL ON SHEET 7.1: |
| CLARIFY FASTENING OF THE UNIT TO THE CONCRETE SLAB. |
| PROVIDE DETAIL SHOWING HOW THE 3/8" BOLTS ARE ATTACHED |
| TO THE BASE OF THE UNIT. SPECIFY HOW MUCH EMBEDMENT |
| INTO THE CONCRETE SLAB IS REQUIRED FOR THE 3//8" SLEEVE |
| ANCHORS. CLEARLY SPECIFY NUMBER OF FASTENER REQUIRED ON |
| EACH SIDE. CLARIFY WHY ONLY SPECIFYING FASTENERS ON TWO |
| SIDES OF THE UNIT. PROVIDE CALCULATIONS SHOWING THAT |
| FASTENING ON ONLY TWO SIDES IS ADEQUATE TO RESIST THE |
| WIND LOADS. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER CLEARLY SPECIFYING |
| HOW EACH COMMENT IS ADDRESSED TO EXPEDITE THE REVIEW |
| PROCESS. |
| ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |