2017-07-11 08:04:49CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. SHOW LOCATION OF ELECTRICAL SERVICE ON PLAN. FBC
 107.2.1
 2. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. MASTER CLOSETS SHOW
 RECESS LIGHTS. PROVIDE CORRECTION. NEC 410.16(B), FBC
 RE4003.12
 3. SMOKE/CO ALARMS ARE REQUIRED TO BE IN THE IMMEDIATE
 VICINITY OUTSIDE THE BEDROOMS. THE CURRENT PLACEMENT IN
 BOTH HALLWAYS OUTSIDE THE BEDROOMS APPEARS THAT IT IS
 TOO FAR FROM THE MASTER BEDROOMS. PROVIDE CORRECTION.
 FBC R314.3
 4. NOTE ON PLAN STATES THAT ALL RECEPTACLES SHALL HAVE
 TAMPER RESISTANT PROTECTION PER NEC 406.11. THIS CODE
 SECTION DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES.
 PROVIDE CORRECTION. NEC 406.12; FBC RE4002.14
 5. PROVIDE COMPLIANCE WITH ENERGY CONSERVATION FOR
 LIGHTING: "A MINIMUM OF 75 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICACY LAMPS". A NOTE ON PLAN WILL SUFFICE.
 FBC EC R404.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  