2017-07-11 08:04:49 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: |
| |
| 1. SHOW LOCATION OF ELECTRICAL SERVICE ON PLAN. FBC |
| 107.2.1 |
| 2. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND |
| PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| PERMITTED IN CLOTHES CLOSETS. MASTER CLOSETS SHOW |
| RECESS LIGHTS. PROVIDE CORRECTION. NEC 410.16(B), FBC |
| RE4003.12 |
| 3. SMOKE/CO ALARMS ARE REQUIRED TO BE IN THE IMMEDIATE |
| VICINITY OUTSIDE THE BEDROOMS. THE CURRENT PLACEMENT IN |
| BOTH HALLWAYS OUTSIDE THE BEDROOMS APPEARS THAT IT IS |
| TOO FAR FROM THE MASTER BEDROOMS. PROVIDE CORRECTION. |
| FBC R314.3 |
| 4. NOTE ON PLAN STATES THAT ALL RECEPTACLES SHALL HAVE |
| TAMPER RESISTANT PROTECTION PER NEC 406.11. THIS CODE |
| SECTION DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES. |
| PROVIDE CORRECTION. NEC 406.12; FBC RE4002.14 |
| 5. PROVIDE COMPLIANCE WITH ENERGY CONSERVATION FOR |
| LIGHTING: "A MINIMUM OF 75 PERCENT OF THE LAMPS IN |
| PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE |
| PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| ONLY HIGH EFFICACY LAMPS". A NOTE ON PLAN WILL SUFFICE. |
| FBC EC R404.1 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |