2017-07-18 18:07:53NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEE IS DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- SQUARE FOOTAGE ON THE PROJECT AREA ON SHEET 2.1 IS
 MISSING THE AREA FOR THE COVERED PATIO. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- PROJECT DATA ON SHEET 2.1 IS MISSING THE ATTIC LIVE
 LOAD AS REQUIRED BY NOTES "B" AND "G" OF TABLE R301.5
 FBC-5TH EDITION (2014).
  
 4- PROVIDE SPECIFICATIONS FOR THE GARAGE DOOR LEADING
 TO THE GREAT ROOM. DOOR NEEDS SELF CLOSING DEVICE AS
 REQUIRED BY SEC. R302.5.1 FBC-RESIDENTIAL.
  
 5- REVISE DIMENSION "A" ON COMPONENTS AND CLADDING
 INFORMATION ON SHEET 4.1 AND 5.1. ACCORDING TO NOTE ON
 FIGURE R301.2(7) OF FBC-RESIDENTIAL THE DIMENSION "A"
 IS 4 FEET IN ALL CASES NOT 3 FEET. REVISE AS REQUIRED.
  
 6- REVISE GARAGE DOORS DESIGN PRESSURES SHOWN ON SHEET
 4.1 AND 5.1. ACCORDING TO NOTES ON PLANS SUBMITTED THE
 DESIGN PRESSURES SHOWN ARE BASED ON TABLE R301.2(4)
 FBC-RESIDENTIAL. DESIGN PRESSURES SHOWN DON'T
 CORRESPOND TO THE REQUIRED DESIGN PRESSURES WHEN THE
 PRESSURES ARE MULTIPLIED BY THE 1.21 COEFFICIENT TO
 REPRESENT THE EXPOSURE "C". REVISE AS REQUIRED.
  
 7- DRAWINGS 7.1, 8.1 AND 9.1 NEED THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AS
 REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS.
  
 8-ENERGY CALCULATIONS SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE
 BOTTOM OF FORM AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION # (604700) AS REQUIRED BY SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) ENERGY CALCULATIONS NEED TO BE DONE FOR THE ACTUAL
 ORIENTATION OF THE BUILDING NOT WORST CASE. REVISE ITEM
 #5 AS REQUIRED BY SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 D) REVISE WALL TYPE ON ITEM #9(B) FOR THE ADJACENT
 WALL. PLANS CALL FOR METAL FRAMING ON ONE SIDE AND WOOD
 FRAMING ON THE OTHER SIDE. SEC. 101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 E) HEATING INFORMATION SHOWN ON ITEM #13 DOESN'T T
 MATCH INFORMATION SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F) CONTRACTOR TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD AS REQUIRED BY SEC. R405.4.3
 FBC-ENERGY CONSERVATION.
  
 G) REVISE WALLS AND WINDOWS ORIENTATION SHOWN ON PAGE 3
 OF 5. COORDINATE WITH ITEM #8(C) ABOVE. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H) REVISE THE DOORS INFORMATION SHOWN ON PAGE 3 OF 5.
 WHERE ARE THE INSULATED DOORS?. SEE PLANS AND PRODUCT
 APPROVALS SUBMITTED. DOORS WITH GLAZING NEED TO BE
 CONSIDERED IN THE WINDOWS AREA AS REQUIRED BY SEC.
 R405.5.3.3 FBC-ENERGY CONSERVATION. REVISE AS REQUIRED.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON ITEM #7 IS REQUIRED WHEN THE
 ENERGY CALCULATIONS ARE NOT USING THE SOFTWARE DEFAULT
 FACTOR.
  
 9- REVISE LOCATION OF CARBON MONOXIDE ALARMS TO COMPLY
 WITH SEC. R315.1 FBC-RESIDENTIAL.
  
 10- REVISE LOCATION OF SMOKE ALARMS TO COMPLY WITH SEC.
 R314.3 FBC-RESIDENTIAL.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 12- ROOF TILE UNDERLAYMENT FL11288-R15 SUBMITTED:
 CLEARLY MARK SPECIFIC UNDERLAYMENT INSTALLATION SHOWING
 THE DESIGN PRESSURES OF PROPOSED INSTALLATION TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: SEE PAGES 5,6 AND 7 OF
 EVALUATION REPORT SUBMITTED. MARK SPECIFIC APPLICATION
 #.
  
 13- TRUSS PACKAGE SUBMITTED:
 A) TRUSS LAYOUT DOESN'T MATCH ENGINEER'S OF RECORD ROOF
 FRAMING PLAN. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
  
 B) DESIGN LOADS DON'T MATCH DESIGN CRITERIA SPECIFIED
 BY THE ENGINEER OF RECORD. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 C) COMPLETE TRUSS PACKAGE TO BE REVIEWED AND APPROVED
 IN WRITING BY THE ENGINEER OF RECORD PRIOR TO SUBMITTAL
 T THIS OFFICE. SEC. 107.3.4.2 CITY AMENDMENTS.
  
 D) TRUSS LAYOUT AND ALL INDIVIDUAL TRUSS DRAWINGS NEED
 TO BE SIGNED AND SEALED AND HAVE THE TRUSS ENGINEER
 INFORMATION IN ALL DRAWINGS AS REQUIRED BY FAC
 61G15-31.003.
  
 ****PLEASE PROVIDE RESPONSE LETTER CLEARLY SPECIFYING
 HOW EACH COMMENT IS ADDRESSED TO EXPEDITE THE REVIEW
 PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  