Plan Review Notes
Plan Review Notes For Permit 17060837
Permit Number 17060837
Review Stop M
Sequence Number 1
Notes
Date Text
2017-06-23 16:28:001ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060837
 6/23/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M0.2: PLEASE LABEL THE AC SYSTEMS CORECTLY IN THE
 SCHEDULE AS EITHER 1, 2, OR 3. CURRENTLY THEY ARE ALL
 LABELED AHU/CU-1.
  
 2) M0.2: IT APPEARS AC-3 AT 5-TONS OF COOLING AND 10KW
 HEAT IS OVERSIZED WHEN COMPARED WITH THE AC
 CALCULATIONS WHICH SHOWS COOLING AT 3.2 TONS AND
 HEATING AT 3.6 KW- SEE SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION. PLEASE NOTE THAT THE HEAT STRIPS FOR AC-
 1 & 2 ARE ALSO OVERSIZED PER THE CALCS.
  
 3) M1.1: A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF AHU-3 UNLESS MANUFACTURER'S SPECIFICATIONS
 INDICATE THAT THE SYSTEM IS INCAPABLE OF PRODUCING OVER
 2000 CFMS OF SUPPLY AIR- SECTION 606.2.1.
  
 4) M1.1: PROVIDE THE CLEARANCE DISTANCE MEASUREMENTS
 FROM THE O/A INTAKE OPENINGS TO THE PARKING AND DRIVE
 AREAS- SECTION 401.4, AND FROM THE EF-1 OUTLET TO THE
 O/A INTAKE ON THE NORTH SIDE- SECTION 501.3.1.
  
 5) M1.1: INDICATE HOW THE O/A INTAKES WILL BE
 PROTECTED- SECTION 401.5.
  