Plan Review Notes For Permit 17060837 |
Permit Number |
17060837 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-06-23 16:28:00 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17060837 | | 6/23/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) M0.2: PLEASE LABEL THE AC SYSTEMS CORECTLY IN THE | | SCHEDULE AS EITHER 1, 2, OR 3. CURRENTLY THEY ARE ALL | | LABELED AHU/CU-1. | | | | 2) M0.2: IT APPEARS AC-3 AT 5-TONS OF COOLING AND 10KW | | HEAT IS OVERSIZED WHEN COMPARED WITH THE AC | | CALCULATIONS WHICH SHOWS COOLING AT 3.2 TONS AND | | HEATING AT 3.6 KW- SEE SECTION C403.2.2 FBC-14 ENERGY | | CONSERVATION. PLEASE NOTE THAT THE HEAT STRIPS FOR AC- | | 1 & 2 ARE ALSO OVERSIZED PER THE CALCS. | | | | 3) M1.1: A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR | | SYSTEM OF AHU-3 UNLESS MANUFACTURER'S SPECIFICATIONS | | INDICATE THAT THE SYSTEM IS INCAPABLE OF PRODUCING OVER | | 2000 CFMS OF SUPPLY AIR- SECTION 606.2.1. | | | | 4) M1.1: PROVIDE THE CLEARANCE DISTANCE MEASUREMENTS | | FROM THE O/A INTAKE OPENINGS TO THE PARKING AND DRIVE | | AREAS- SECTION 401.4, AND FROM THE EF-1 OUTLET TO THE | | O/A INTAKE ON THE NORTH SIDE- SECTION 501.3.1. | | | | 5) M1.1: INDICATE HOW THE O/A INTAKES WILL BE | | PROTECTED- SECTION 401.5. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|