2017-06-21 08:32:54 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #17060813 |
| 6/21/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE COMPANY THAT PREPARED THE AC AND ENERGY |
| CALCULATIONS- ENERGY HOUSE TECHNOLOGY- CANNOT DRAW THE |
| AC PLAN FOR THE NEW OFFICE AC SYSTEMS UNLESS THE |
| COMPANY IS FL. STATE LICENSED AS AN AC OR MECHANICAL |
| CONTRACTOR, AND IS THE INSTALLING CONTRACTOR ON THE |
| PROJECT- SECTION 105.3.1 WEST PALM BEACH AMENDMENTS TO |
| THE FBC. I PERFORMED A LICENSE SEARCH ON THE DPBR |
| WEBSITE AND NO CONTRACTORS LICENSE EXISTS FOR EITHER |
| ENERGY HOUSE TECHNOLOGY OR THE COMPANY OWNER BRUCE |
| TSCHOSIK. THE PLAN SUBMITTED BY ENERGY HOUSE TECHNOLGY |
| IS INCOMPLETE AND NOT DRAWN TO A MINIMUM 1/8" SCALE- |
| SECTION 107.2.1.4. ADDITIONAL DEFICIENCIES AND |
| INFORMATION MISSING FROM THE PLANS INCLUDE: EQUIPMENT |
| SCHEDULES, AIR DISTRIBUTION SCHEDULE, VENTILATION |
| CALCULATIONS, LOCATIONS AND INSTALLATION DETAILS FOR |
| THE AIR HANDLERS AND CONDENSERS, RETURN AIR SYSTEM |
| DETAILS, DUCTWORK SPECIFICATIONS AND SUPPORT AND |
| HANGING DETAILS, OUTDOOR AIR DUCT SIZES, O/A OPENING |
| PROTECTION, O/A SHUTOFF CONTROLS, CONDENSATE DISPOSAL, |
| REFRIGERANT PIPING SPECIFICATIONS, RF PIPING RUNS AND |
| PIPE PROTECTIONS, WIND LOAD ENGINEERING FOR |
| INSTALLATION OF THE EXTERIOR CONDENSERS ETC. |
| |
| 2) NO PERMITS EXIST, NOR HAVE ANY PERMIT APPLICATIONS |
| BEEN SUBMITTED FOR THE PROPOSED PROJECT TO CONVERT THE |
| EXISTING UNCONDITIONED WAREHOUSE TO OFFICE SPACE. THE |
| MECHANICAL REVIEW IS STOPPED UNTIL COMPLETE BUILDING |
| AND MEP PLANS ARE SUBMITTED. PLEASE SEE SECTIONS |
| C101.4.4 AND C101.4.5 FBC-14 ENERGY CONSERVATION: |
| SUBMITTED FOR REVIEW ARE ENERGYGAUGE COMPLIANCE REPORTS |
| USING THE ASHRAE 90.1 -2010 ENERGY COST BUDGET OPTION. |
| ALL CONSTRUCTS FOR THE BUILDING ENVELOPE AND MEP |
| SYSTEMS INFORMATION SHOWN ON THE SUBMITTED ASHRAE INPUT |
| DATA REPORT MUST ALSO BE SHOWN ON THE ARCHITECTURAL AND |
| MEP PLANS. |
| |